Page 20 of 38
939502326 Rev G
'L' Configuration
'T' Configuration
In-line Configuration
Process for Carpet and Tile Floor tape
application ONLY
•
Floor glide to be cleaned using Acetone soaked cloth prior
to applying pressure sensitive tape or carpet gripper tape.
•
Attach pressure sensitive tape for 24 hours prior to loading.
(Confirm application with local building codes)
or
•
Attach carpet gripper tape for 24 hours prior to loading.
(Confirm application with local building codes)
CAUTION: When installing Steelcase V.I.A. over Steelcase Low-Profile floor, floor
guide (style number FEFG) MUST be applied to all leveler screws to distribute
wall / applied furniture loading. Failure to consider application and loading
may result in wall disengagement from ceiling track, resulting in personal injury.
NOTE: When the V.I.A. Wall is fully loaded, the wall has the potential to deliver 1,200 pounds per leveler screw to floor
condition. Leveler screws loaded to 1,200 pounds will exert local pressure loading of 11,000 PSI. Floor type / Steelcase
product application must be properly matched in accordance with local building codes and floor condition to avoid flooring
damage and ensure proper performance of Steelcase Wall Systems.
Chalk Line
Floor Guide
Base
Track
Base
Track
Chalk Line
Chalk Line
Floor Guides
Chalk Lines
Floor Guides
Base
Track
Floor Guide
Pressure Sensitive Tape
or Carpet Gripper Tape
Mechanical fastening ONLY
•
Consult local building codes.
NOTE: Fasteners shown for
mechanical fastening only.
NOTE: Fasteners shown for
mechanical fastening only.
NOTE: Fasteners shown for
mechanical fastening only.
4" Min.
2" Max.
1" Min.
6" Min.
1" Min.
6" Min.
Carpet Application:
Hard Floor
Application:
Structural Fastener
NOTE: Mounting hardware must be specified/verified by the designated design professional by the AHJ.
Floor Guide
NOTE: Floor guides may be needed at vertical posts and junctions when adjacent to a door frame.