Steca XP-COMPACT
XP-COMPACT
V5.5
14/57
4.3 Light Emitting Diodes (LED)
LED
Marking
LED lit
LED blinks
1 AC
IN
Voltage
corresponding to
self-adjusted
values is at the AC
IN input.
A voltage outside the self-adjusted
values is at the AC IN input, or the XP-
COMPACT is in synchronization
phases
2 CHARGER
Battery charger is
working
The battery charger is locked OFF
(see chap. 4.7) or provisory out of
order. In that last case it will restart
within 10 seconds
3
SOLAR
CHARGE
This function is not offered for the XP-Compact
4 Program
Program mode for
Aux. Contact
5
Contact
active
Auxiliary Contact is
activated
6
Contact
manual
Aux. Cont.
manually activated
7 TRANSFER
Transfer system is
active. In- coming
voltage is being
sent directly to AC
OUT outlet
Transfer (bypass) is disabled (see
chap. 4.8)
8 AC
OUT
There is a voltage
at the AC OUT
outlet
The Inverter is in Standby-Mode
9 INVERTER
Inverter
is
working
Forced Inverter Mode (see chap. 4.6)
10 Over
Temp.
For the time being
the XP-COMPACT
is out of service
because of
overheating.
11 Overload
The XP-COMPACT
is out of service
because of
overload or short-
circuit
12
Batt.
Low/High
Battery voltage is
too low
Battery voltage is or was to high
13 OFF
XP-COMPACT is
turned off. Turning
it back on is only
possible manually.
XP-COMPACT is for the time being
turned off. Turning it back on will
follow automatically !
14 EQUALIZE
Battery equalizing
is set
15–18
State of charge of
the battery
LED 15 – Absorption time is running
Содержание XPC 1400-12
Страница 27: ...Steca XP COMPACT XP COMPACT V5 5 27 57 8 Technical Data ...
Страница 41: ...Steca XP COMPACT XP COMPACT V5 5 41 57 4 2 Anzeigen und Bedienelemente für der Fernsteuerung Remote control ...
Страница 56: ...Steca XP COMPACT XP COMPACT V5 5 56 57 8 Technische Daten ...
Страница 57: ...Steca XP COMPACT XP COMPACT V5 5 57 57 ...
Страница 58: ......
Страница 59: ......
Страница 60: ...714828 ...