I N T E N D E D U S E
8
Installation overview
General
1.
Installation of this space blower should be carried out by trained and qualified
personnel.
2.
Any work related to installation of this space blower must comply with local code and
regulation regarding safety and prevention of accidents.
WARNING. Risk of electric shock
.
Power supply must be disconnected during installation.
Main power should be connected only after all installation steps have been completed and
properly verified.
Installation steps :
1.
Positioning & mounting of
Space blower/humidifier
2.
If Remotely installed from humidifier
a.
Steam line installation
b.
Condensate line installation
c.
Power supply installation
d.
Control signal installation
Installation – step 1
IER Positioning & Mounting
General guidelines for positioning
Space blower
should be positioned so that:
Length of the steam line (or hose) is as short as possible,
In case steam hose is used, the bend radius of 12in (300mm) is ensured
Space blower is easily accessible for service
CAUTION: Risk of water damage.
Ensure that the surrounding area below and
around the space blower will not be damaged by any possible water projection.
CAUTION:
Do not install Space blower above any electrical equipment, as water leak
from connection or abnormal operation can cause malfunction or short circuit.
IER
maximum ambient conditions:
Temperature: 41°F to 122°F [+5 to +50°C]
Relative Humidity: 90%RH max (non condensing)
Ingress Protection for
SB space blower
standard enclosure: IP20
section
3