I N S T A L L A T I O N
11
Installation – step 4
Steam line installation
Built-in SB
Steam line and condensate return are factory installed on Built-in Space blower.
Remote SB
Figure 7 – Steam & condensate line for Remote SB
Installation steps :
1.
Install the steam hose or rigid steam pipe between the steam humidifier and the Space
blower.
Note: when using rigid steam pipe (stainless steel or copper) it is a good practice to
install a small length of steam hose in between steam humidifier and rigid pipe and then
Space blower for ease of installation and service.
Allow for a slope of 2° minimum.
2.
Secure all connexion with hose clamps
3.
Connect the condensate return from Space blower and provide a condensate trap of 8in
[200mm] minimum as shown on above figure.
Allow for a slope of 2° minimum.
Condensate return can be re-directed to the steam humidifier, or to an open drain.
4.
Secure all connexion with hose clamps