I N S T A L L A T I O N
Verification before start-up
Warning
For safety and warranty reasons, Installation and service of this humidifier should be carried out by
trained and qualified personnel.
Any work related to installation and service of this humidifier must comply with local code and
regulation regarding safety and prevention of accidents.
Risk of electric shock
.
Disconnect power supply before verification.
Risk of burnt, flooding or malfunction.
Steam lines should not have any restriction or blockage
that may cause a burst of pressure in the steam line.
Risk of flooding.
In order to avoid any risk of flooding
steamOvap
recommends an air proving
switch installation in ventilation duct; and a High limit humidistat in the duct downstream the
steam ramp if air supply temperature is below 68°F [20°C].
Risk of freezing
. Plan an anti-freeze system in case of installation in a location that would be
exposed to outside conditions and susceptible of freezing.
Check list
Mounting
o
Check mounting to verify that the
steamOres
humidifier is levelled and securely
supported before filling with water.
o
In case of
steamOres
directly to the ventilation duct, confirm that there is no vibration or
oscillation that would impair it operation.
Water supply
o
Verify that all piping connections have been completed as recommended and that water
pressure is available.
o
Once water shut off valve is open, verify for any possible leak.
Drain
o
Verify that all drain piping has been completed as recommended and that an open drain
deported from
steamOres
humidifier is provided.
Steam line
o
Verify that all steam piping has been completed as recommended and that a slope of
minimum 2° is provided.
o
Ensure that there is no sag or kink or any possible obstruction in the steam line.
Power supply
o
Verify that
steamOres
humidifier has been connected to standard 120Vac outlet or to
dedicated disconnect switch
o
Identify circuit breaker and confirm that size of circuit breaker is compatible with
steamOres
humidifier current rating.
Control circuit
o
Verify that safety controls such as air proving switch and (when applicable) Hi limit
humidistat have been connected.
o
Verify that an On/Off dry contact, or external control signal demand or RH% sensor is
connected to the control terminals.
Once all above verification has been completed and found satisfactory you can powered up the
steamOres
humidifier.
21