4.7.2 Switching Output x: Upper Limit (Set Point)
The upper limit for switching output x (set point) is set in sub-menu:
Settings OUTX
Out X
RXWB
Main menu meas. value
Meas.value
BBBB
Upper limit 1
63
)+ )+L
BBBB
&&
Parameter
BBBB
Ź
Ź
Ź
Range
0 °C to 100 °C
(32 °F to 212 °F)
Set point for OUT x
Note:
-
The set point must be set within the measuring range (see menu
Basic
extended functions
E()
).
-
If the switching characteristic is set to
window
,
is displayed.
The set value represents the upper window limit.
-
If the switching characteristic is set as
frequency output
,
is
displayed. The set value represents a frequency of 100 Hz.
4.7.3 Switching output x: Lower Limit (Reset Point)
The lower limit for switching output x (set point) is set in sub-menu:
Settings OUTX
Out X
RXWB
Main menu meas. value
Meas.value
BBBB
Reset point X
63
)+ )+L
BBBB
&&
Parameter
BBBB
Ź
Ź
Ź
Range
0 °C to 100 °C
(32 °F to 212 °F)
Reset point for OUT x
Note:
-
The reset point
U3
must be set within the measuring range.
-
If the switching characteristic is set to
window
,
is displayed.
The set value represents the lower window limit.
-
If the switching characteristic is set as
frequency output
,
is
displayed. The set value represents a frequency of 1 Hz.
4.7.4 Switching Output x: Delay for Set Point
Menu
Extended Functions EF1
provides further settings for switching output x. The menu is located on
the second sub-menu level.
The delay time for set point and reset point avoids too many false alarms in case of fluctuating conditions.
The delay for the set point is set in the following menu:
Extenden functions
EF X
()B
Delay for OUTX on
Delay SP X
G6B
Parameter
BBB
Settings OUTX
Out X
RXWB
Ź
Ź
Ź
Main menu meas. value
Meas. value
BBBB
Ź
Range:
0…100 seconds
Time in seconds which the signal must at least remain to enable the switch to
operate.
Note:
-
If the output characteristic is set to
Window
the value represents the time
delay for the signal remaining within the measurement window.
-
If the output characteristic is set to
Frequency Output
, this value has no
effect.