D2275-02-02 SEM315 CN4978 WEB User guide 

 

 

1.0 DESCRIPTION

 

 
The SEM315 is a HART Din Rail temperature transmitter that accepts commonly used temperature 
sensor, slidewire transducer or millivolt signal and converts the output to the industry standard (4 to 
20) mA transmission signal. 
 
The software package M-config or a Hart Communicator with the necessary “Device Description” can 
be used to program the unit.  
 
 

 

2.0 SPECIFICATION @ 20 °C

 

 

 

2.1 RTD INPUT (Pt100) 2, 3 OR 4 WIRE 

 
Sensor Range 

 

 

(-200 to 850) °C (18 to 390) 

 

Minimum Span 

1

 

 

 

25 °C 

Linearisation 

 

 

BS EN60751 (IEC 751) BS 1904  

 

 

 

 

(DIN 43760), JISC 1604, CUSTOM [X] 

3

 

Max Lead Resistance 

 

50 

 per leg (balanced for 3 wire) 

Basic Measurement Accuracy 

2

 

±0.01 % FRI ±0.07 % Rdg 

 

 

 

 

(FRI = Full Range Input) 

RTD Excitation Current 

 

(300 to 500) µA 

Thermal Drift 

 

Zero 

0.008 °C / C 

 

 

 

Span 

0.01% / °C 

 

 

2.2 THERMOCOUPLE INPUT 

 

Thermocouple Type 

Measuring Range

4

 °C 

Minimum Span

1

 °C 

TC Type K 

-200 to 1370 

50 

TC Type J 

-200 to 1200 

50 

TC Type T 

-210 to 400 

25 

TC Type R 

-10 to 1760 

100 

TC Type S 

-10 to 1760 

100 

TC Type E 

-200 to 1000 

50 

TC Type L 

-100 to 600 

25 

TC Type N 

-180 to 1300 

50 

TC Type [X]

3

 

User defined 

 

 
Linearisation 

 

 

BS EN60584-01 BS 4937/IEC 584-1 

 

 

 

 

(multi segment Polynomials) 

Basic Measurement Accuracy 

2

 

0.04 % FRI ±0.04 % RDG or 0.5 °C  

 

 

 

 

(whichever is greater) 

Thermal Drift 

 

 

Span 0.01 % / °C 

Cold Junction Error   

 

±0.5 °C 

Cold Junction Tracking 

 

0.05 °C / °C 

Cold Junction Range 

 

(-40 to +85) °C 

 

Page1 

 

 

2. 3 MILLIVOLT INPUT

 

 
Input 

 

 

 

Voltage Source 

Range 

 

 

 

(-10 to 75) mV 

Characterisation 

 

 

Linear, Custom [X] 

3

 

Minimum Span 

 

 

5 mV 

Basic Measurement Accuracy 

2

  

±10 µV ±0.07 % Rdg 

Input Impedance 

 

 

10 M

 

 

Thermal Drift 

 

Zero 

0.1 µA / °C 

 

 

 

Span 

0.01 % / °C 

 

 

2.4 SLIDEWIRE INPUT

 

 
Input 

 

 

 

3 Wire potentiometer 

Resistance Range 

(10 to 390) 

 (End to End) Larger values can be 

accommodated by fitting a link, see Figure 2. 

Characterisation 

 

 

Linear, Custom [X] 

3

 

Minimum Span 

1

 

 

 

5 % of FRI 

Basic Measurement Accuracy 

2

 

0.1 % FRI 

Thermal Drift 

 

Zero 

0.005 % of span / °C  

 

 

 

Span 

0.01 % / °C 

Range 

 

 

 

(0 to 100) % 

 

 

2.5 OUTPUT

 

 
Burnout Levels 

 

 

Low 3.75 mA , High 21.5 mA 

Input out of Range   

 

Low 3.8 mA, High 20.5 mA 

Output range 

 

 

(4 to 20) mA, Min. 3.75 mA, Max. 21.5 mA 

Accuracy   

 

 

±5 µA 

Thermal Drift 

 

 

1 µA / °C 

Supply Voltage 

5

 

 

 

(10 to 40) V 

Supply Voltage effect 

 

0.2 µA / V 

Maximum output load 

[(Vsupply-10)/21.5] K

. 250 

 minimum loop load for correct 

HART operation.

5

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Page 2 

24 V

15 V

30 V

40 V

660

500

250

1400

10 V

0

NO HART

OPERATION

NOT RECOMMENDED

SUPPLY

VOLTAGE

MAXIMUM LOAD ( 

 )

OPERATION

Содержание SEM315

Страница 1: ...TTER Status Instruments Ltd Green Lane Business Park Tewkesbury Glos GL20 8DE Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk INDEX SECTION CONTENTS PAGE NO 1 0 DESCRIPTION 1 2 0 SPECIFICATION 1 3 3 0 INSTALLATION 4 5 4 0 HART PROGRAMMING 5 7 ...

Страница 2: ...e X 3 User defined Linearisation BS EN60584 01 BS 4937 IEC 584 1 multi segment Polynomials Basic Measurement Accuracy 2 0 04 FRI 0 04 RDG or 0 5 C whichever is greater Thermal Drift Span 0 01 C Cold Junction Error 0 5 C Cold Junction Tracking 0 05 C C Cold Junction Range 40 to 85 C Page1 2 3 MILLIVOLT INPUT Input Voltage Source Range 10 to 75 mV Characterisation Linear Custom X 3 Minimum Span 5 mV...

Страница 3: ... be mounted in any orientation Care must be taken when locating the transmitter to ensure the ambient temperature remains within the specified operating range Figure 1 shows the mechanical layout of the transmitter Fig 1 All Dimensions in mm 3 2 ELECTRICAL Connections to the transmitter are made to the tension clamp terminals provided on the front face Output signal wiring should use screened twis...

Страница 4: ...g terminals as shown 4 0 HART PROGRAMMING Consult HART website for more details www hartcomm org 4 1 CONNECTION ARRANGEMENT FOR HART COMMUNICATOR Fig 3 1a Page 5 Fig 3 1b 4 2 CONNECTION ARRANGEMENTS FOR HART MODEM e g M CONFIG Fig 3 2a Page 6 R 250 L mA Current Meter Power Supply Black Connector HART Modem To PC 1 2 Red Connector ...

Страница 5: ...or or HART modem across the load in Figure 3 1a and 3 2a respectively Page 7 ALSO AVAILABLE Smart In Head Temperature Transmitters Din Rail Mounted Temperature Transmitters Panel Field Temperature Indicators Temperature Probes Trip Amplifiers Signal Conditioners And many other products For further information on all products Status Instruments Ltd Green Lane Business Park Tewkesbury Glos GL20 8DE ...

Отзывы: