D2275-02-02 SEM315 CN4978 WEB User guide 

Notes 

1

 

Any span may be selected but full accuracy is only guaranteed for spans greater than the 
minimum recommended. 

2

 

Includes the effect of calibration, linearisation and repeatability. 

3

 

Custom characterisation is available pre-programmed at the factory. Contact your nearest 
Sales office. 

4

 

Consult Thermocouple reference tables for practical temperature ranges. 

5

 

For supply voltages over 30V, a minimum loop load of 500 

 is necessary. 

 

 

2.6 GENERAL

 

 
Input/Output Isolation 

 

500 VAC  

Time Constant (Filter Off) 

 

0.5 secs (to 90 % of final value) 

Filter Factor Programmable 

  

Off / selectable between 1 and 32 seconds / or Adaptive 

Warm-up Time 

 

 

120 seconds to full accuracy 

 

ENVIRONMENTAL 

Ambient Operating Range 

 

(-40 to 85) °C 

Ambient Storage Temperature  

(-50 to 90) °C 

Ambient Humidity Range 

 

(10 to 95) % RH non condensing 

 

EMC

 

 

 

BS EN 61326 

 

MECHANICAL 

Enclosure  

 

DIN Rail mounted to fit DIN EN 50022-35 

Material   

 

ABS 

Weight 

 

 

70 g 

Dimensions 

 

(90 x 99 x 18.5) mm 

Flammability 

 

UL94-V0 

Connections 

 

Tension clamp two terminals and 3.5 jack for comms. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Page 3 

 

3.0 INSTALLATION

 

 

 

3.1 MECHANICAL

 

 
The transmitter is designed to mount onto a standard Din Rail. The transmitter should be installed 
with adequate protection from moisture and corrosive atmospheres. The transmitter may be mounted 
in any orientation. 
 
Care must be taken when locating the transmitter to ensure the ambient temperature remains within 
the specified operating range. Figure 1 shows the mechanical layout of the transmitter 
 

Fig 1

 

 

(All Dimensions in mm) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

3.2 ELECTRICAL

 

 
Connections to the transmitter are made to the tension clamp terminals provided on the front face. 
Output signal wiring should use screened twisted pair. It is recommended that screened cable is used 
for the input signal wires for cable runs greater than one metre. For Pt100 inputs all input wires must 
have the same core diameter to maintain equal resistance in each wire. 
 
Figure 2 shows the method of connection to provide a (4 to 20) mA current loop output. The output 
loop has a voltage power supply used to provide loop excitation. The load symbol represents other 
equipment in the loop, normally indicators, controllers or loggers. Care must be taken when designing 
the (4 to 20) mA circuit to ensure that the total voltage requirements of all the equipment in the loop 
added together, does not exceed the power supply voltage. If a number of instruments are connected 
in the loop, ensure that only one instrument is tied to ground. Grounding the loop at two points will 
cause a short circuit of part of the loop leading to measurement errors. To maintain CE compliance 
the transmitter should be mounted in an enclosure to prevent access to the transmitter during normal 
operation. 
 

Page 4 

18.25

99.5

90.0

6

7

8

9

10

5

4

3

2

1

Содержание SEM315

Страница 1: ...TTER Status Instruments Ltd Green Lane Business Park Tewkesbury Glos GL20 8DE Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk INDEX SECTION CONTENTS PAGE NO 1 0 DESCRIPTION 1 2 0 SPECIFICATION 1 3 3 0 INSTALLATION 4 5 4 0 HART PROGRAMMING 5 7 ...

Страница 2: ...e X 3 User defined Linearisation BS EN60584 01 BS 4937 IEC 584 1 multi segment Polynomials Basic Measurement Accuracy 2 0 04 FRI 0 04 RDG or 0 5 C whichever is greater Thermal Drift Span 0 01 C Cold Junction Error 0 5 C Cold Junction Tracking 0 05 C C Cold Junction Range 40 to 85 C Page1 2 3 MILLIVOLT INPUT Input Voltage Source Range 10 to 75 mV Characterisation Linear Custom X 3 Minimum Span 5 mV...

Страница 3: ... be mounted in any orientation Care must be taken when locating the transmitter to ensure the ambient temperature remains within the specified operating range Figure 1 shows the mechanical layout of the transmitter Fig 1 All Dimensions in mm 3 2 ELECTRICAL Connections to the transmitter are made to the tension clamp terminals provided on the front face Output signal wiring should use screened twis...

Страница 4: ...g terminals as shown 4 0 HART PROGRAMMING Consult HART website for more details www hartcomm org 4 1 CONNECTION ARRANGEMENT FOR HART COMMUNICATOR Fig 3 1a Page 5 Fig 3 1b 4 2 CONNECTION ARRANGEMENTS FOR HART MODEM e g M CONFIG Fig 3 2a Page 6 R 250 L mA Current Meter Power Supply Black Connector HART Modem To PC 1 2 Red Connector ...

Страница 5: ...or or HART modem across the load in Figure 3 1a and 3 2a respectively Page 7 ALSO AVAILABLE Smart In Head Temperature Transmitters Din Rail Mounted Temperature Transmitters Panel Field Temperature Indicators Temperature Probes Trip Amplifiers Signal Conditioners And many other products For further information on all products Status Instruments Ltd Green Lane Business Park Tewkesbury Glos GL20 8DE ...

Отзывы: