background image

D2588-01-03  CN5602 SEM1605P User Guide

SUPPLY (Vs)  = (10 to 30) V dc

MAX  LOAD

KΩ = [(Vs – 10)/20] 

OUTPUT
2 Wire (4 to 20) mA 

INPUT CONNECTION

RTD wire must be equal length and type .
To maintain CE compliance cable length must be less than 30 
metres.

 

OUTPUT CONNECTION

Use twisted pair or screened cables for cable lengths greater 
than 30 metres. Max cable length 1000 metres. Ensure loop is 
grounded at one point.

Vs

Loop 
Load

+

-

9

7

8

2

1

 INPUT 

 RTD

Ø 3mm

Screw Driver

Screened Cable

Twisted Pair Cable

TURN OFF SUPPLY BEFORE   WORKING ON ANY ELECTRICAL CONNECTION

SEM1605P Enclosure

Style

DIN 43880 (1 module width)

Material       

Polyamide 6.6 self extinguishing

Terminals

Screw terminal

Cable

2.5 mm Max

Colour

Grey

Ø 3  mm

90 mm

MOUNTING

Screw driver

EN50022 DIN RAIL

56.4 mm

17.5 mm

1
2

11

12

10

9

8

7

4

5

6

1

2

3

To fit or release module

Insert screw driver into

slot and lever latch

away from body

1

2

+ 70 °C Max

- 30 °C Min

1

2

ADJUST

STATE

ADJUST

STATE

+

_

MECHANICAL INSTALLATION

ELECTRICAL  INSTALLATION

USB

SEM1605 P

Отзывы: