Thank You  for  purchasing  this  water  heater.  Properly  installed 

and maintained, it should give you years of trouble free service.

ABBREVIATIONS USED

Abbreviations found in this Instruction Manual include :

• 

ANSI - American National Standards Institute

• 

ASME - American Society of Mechanical Engineers

• 

AHRI - Air Conditioning, Heating and Refrigeration Institute

• 

NEC - National Electrical Code

• 

NFPA - National Fire Protection Association

• 

UL - Underwriters Laboratory

• 

CSA - Canadian Standards Association

QUALIFICATIONS

QUALIFIED INSTALLER OR SERVICE AGENCY

Installation  and  service  of  this  water  heater  requires  ability 

equivalent to that of a Qualified Agency (as defined by ANSI below) 

in the field involved. Installation skills such as plumbing, air supply, 

venting, gas supply and electrical supply are required in addition 

to electrical testing skills when performing service.

ANSI Z223.1:

 “Qualified Agency” - “Any individual, firm, corporation 

or company that either in person or through a representative is 

engaged in and is responsible for (a) the installation, testing or 

replacement  of  gas  piping  or  (b)  the  connection,  installation, 

testing,  repair,  or  servicing  of  appliances  and  equipment;  that 

is experienced in such work; that is familiar with all precautions 

required; and that has complied with all the requirements of the 

authority having jurisdiction.”
If you are not qualified (as defined by ANSI above) and licensed or 

certified as required by the authority having jurisdiction to perform 

a given task do not attempt to perform any of the procedures 

described in this manual. If you do not understand the instructions 

given in this manual do not attempt to perform any procedures 

outlined in this manual.

ICOMM AND BMS/EMS COMPATIBILITY

ICOMM™

This  water  heater  comes  equipped  with  the  iCOMM™  remote 

monitoring system. It allows users to monitor critical operations 

and  diagnose  issues  remotely  using  the  manufacture’s  water 

heater app (available for IOS and Android).
 The iCOMM™ system can automatically notify selected personnel 

via  email  and  or  cellular  phone  text  messages  if  operational 

problems or user defined alert conditions occur. The system is 

expandable to meet the needs of multiple heaters and groups of 

heaters. 

ICC

This water heater is connectable to BACnet or Modbus compliant 

Supervisory  controls  via  the  ICC  BMS  Gateway.  This  allows 

connection  of  the  water  heater  to  local  Building  Management 

Systems using Serial RS-485 (MS/TP) or IP connections. 
To order or to find out more about iCOMM™ or ICC devices, logon 

to the manufacturer’s website at http://www.hotwater.com/ or call 

888-928-3702  (888-WATER02) for more information.

PREPARING FOR THE INSTALLATION

1. 

Read the entire manual before attempting to install or operate 

the  water  heater.  Pay  close  attention  to  the 

General Safety 

Information

 (page 4)

If you don’t follow the safety rules, the 

water heater may not operate safely. It could cause property 

damage, injury and/or death.

• 

This  manual  contains  instructions  for  the  installation, 

operation, and maintenance of the water heater. It also 

contains  warnings  throughout  the  manual  that  you 

must  read  and  be  aware  of. All  warnings  and  all  in-

structions are essential to the proper operation of the 

water heater and your safety. 

• 

Detailed  installation  diagrams  are  also  found  in  this 

INTRODUCTION

manual. These diagrams will serve to provide the in-

staller with a reference. It is essential that all venting, 

water  piping,  gas  piping  and  wiring  be  installed  as 

shown.

• 

Particular attention should be given to the installation 

of thermometers at the locations indicated in the pip-

ing diagrams as these are necessary for checking the 

operation of the water heater.

• 

The principal components of the water heater are iden-

tified  in  Features  and  Components  on  page  8

 in 

this manual. Use this reference to locate and identify 

various components on the water heater.

•  See 

Troubleshooting

  (page 57)

.  By  using  this  check-

list  the  user  may  be  able  to  make  minor  operational 

adjustments  and  avoid  unnecessary  service  calls. 

However, service and diagnostic procedures should be 

performed only by a Qualified Service Agency.

Note: 

Costs to correct installation errors are not covered 

under the limited warranty. See 

Commercial Water 

Heater Limited Warranty

 

(page 76)

.

2. 

Be sure to turn off power when working on or near the electrical 

system of the water heater. Never touch electrical components 

with wet hands or when standing in water.

3.  The installation must conform to all instructions contained in 

this manual and the local code authority having jurisdiction. 

These shall be carefully followed in all cases. Authorities having 

jurisdiction  should  be  consulted  before  installation  begins  if 

there are any questions regarding compliance with local, state 

or national codes.

• 

In  the  absence  of  local  codes,  the  installation  must 

comply  with  the  current  editions  of  the 

National Fuel 

Gas Code

ANSI Z223.1/NFPA 54

 and the 

National Electrical 

Code

NFPA 70

 or 

CAN/CSA-B149.1

,  the 

Natural Gas and 

Propane Installation Code

  and 

CSA C22.1

,  the 

Canadian 

Electrical Code

. All  documents  are  available  from  the 

Canadian Standards Association, 8501 East Pleasant 

Valley Road, Cleveland, OH 44131. NFPA documents 

are also available from the National Fire Protection As-

sociation, 1 Batterymarch Park, Quincy, MA 02269.

4. 

After  reading  this  manual,  if  you  have  any  questions  or  do 

not  understand  any  portion  of  the  instructions,  call  the  toll 

free number on the back cover of this manual for technical 

assistance. In order to expedite your request, please have the 

full Model, Serial and Series numbers of the water heater you 

are working with available for the technician. This information 

is located on the water heater’s rating label.

5. 

Carefully  plan  the  placement  of  the  water  heater.  Examine 

the location to ensure that it complies with the requirements 

in 

Locating the Water Heater

  (page 11)

  and  the 

Rough-In 

Dimensions

 (page 10).

6.  For installation in California this water heater must be braced 

or anchored to avoid falling or moving during an earthquake. 

See instructions for correct installation procedures. Instructions 

may be obtained from California Office of the State Architect, 

1102 Q Street, Suite 5100, Sacramento, CA 95811.

7. 

Massachusetts Code requires this water heater to be installed 

in accordance with 

Massachusetts 248-CMR 2.00: State Plumbing 

Code

 and 

248-CMR 5

. See 

Installing Carbon Monoxide Detectors

 

(page 20).

Содержание SUF 60120 THRU

Страница 1: ...e instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinit...

Страница 2: ...mination Installation 27 Polypropylene Installations 28 AL29 4C Vent Installations 29 Common Direct Venting Requirements 29 Concentric Termination Installation Preparation 30 Concentric Termination In...

Страница 3: ...o not follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in injury or deat...

Страница 4: ...hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS...

Страница 5: ...operation Disconnect gas piping at main gas shutoff valve before leak testing heater Install sediment trap in accordance with NFPA 54 or CAN CSA B149 1 Use joint compound or Teflon tape compatible wit...

Страница 6: ...read and be aware of All warnings and all in structions are essential to the proper operation of the water heater and your safety Detailed installation diagrams are also found in this INTRODUCTION ma...

Страница 7: ...ol Board CCB The CCB monitors the water temperature in the tank and regulates the firing rate to achieve the target temperature set point The firing rate is dictated by the hot water draw proximity to...

Страница 8: ...e water heater is not restricted The control system monitors this switch and will disable heating operation if its contacts are open during a heating cycle 8 Supply gas line connection See the require...

Страница 9: ...rol System Operation page 45 8 Temperature Pressure Relief Valve See Temperature Pressure Relief Valve page 15 9 Temperature Pressure Relief Valve discharge pipe see T P Valve Discharge Pipe Requireme...

Страница 10: ...L V E FRONT 1 NPT WATER OUTLET E X H A U S T AIR INTAKE 18 42 26 90 BACK Figure 5 Rough In Dimensions ROUGH IN DIMENSIONS Model Table 1 Dimensions by Model APPROX SHIP WEIGHT STD APPROX SHIP WEIGHT AS...

Страница 11: ...her replacing an existing water heater or installing the water heater in a new location observe the following critical points 1 The water heater must be located indoors 2 The water heater must not be...

Страница 12: ...urns water heaters water piping and other equipment See Maintenance page 63 for sediment and lime scale removal procedures CIRCULATION PUMPS A circulating pump is used when a system requires a circula...

Страница 13: ...l and propane gas Install a positive lock up gas pressure regulator in the gas supply line if inlet gas pressure can exceed these pres sures at any time If a positive lock up regulator is required fol...

Страница 14: ...square inch 103 kPa and 173 kPa Flow pressures above 25 pounds per square inch 173 kPa or below 15 pounds per square inch 103 kPa will result in improperly sanitized dishes Where pressures are high a...

Страница 15: ...er heater is provided with a properly rated sized and certified combination Temperature Pressure Relief Valve T P valve by the manufacturer The valve is certified by a nationally recognized testing la...

Страница 16: ...y local codes Note Lower PH levels are acidic Do not connect a metal drain line such as copper to the water heater for this reason See Condensate Drain Installation page 39 COMBUSTIBLE MATERIAL STORAG...

Страница 17: ...rea through a design of louver or grille or screen is known it shall be used in calculating the size of opening required to provide the free area specified Where the louver and grille design and free...

Страница 18: ...ommencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 10 The water heater shall have clearances of at least 1 inch 25 mm from the sides and back and 6 inches 150 m...

Страница 19: ...section of the manual are a reference for the openings that provide fresh air into confined spaces only DO NOT refer to these illustrations for the purpose of vent installation See Venting Installati...

Страница 20: ...above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in si...

Страница 21: ...ents page 22 12 Use only factory supplied vent and intake air concentric or low profile terminations See Venting Requirements page 22 13 Do not locate the vent exhaust or intake air terminations where...

Страница 22: ...VC Materials should use ASTM F 493 Grade Cement during severe cold weather To prevent the recirculation of flue gases maintain as much distance as possible between the intake air and vent terminations...

Страница 23: ...te horizontally through a sidewall see Sidewall Termination Installation page PIPE SIZE REQUIREMENTS The water heaters covered in this manual are certified for the use of two three and four inch pipe...

Страница 24: ...ipe transition to three inch pipe at the intake air connection on the water heater as shown in Figure 19 The field installed three inch pipe between the intake air connection and the reducer coupling...

Страница 25: ...cm 18 inches 45 cm in Canada above the average or expected snow level as shown in Figure 22 and Figure 24 page 27 6 When the intake air and or vent piping from multiple water heaters will terminate i...

Страница 26: ...o more than 2 inches 5 cm 11 Return to Power Vent Installation page 23 or Direct Vent Installation page 24 to complete the installation of the intake air and or vent piping between the termination s a...

Страница 27: ...t least 48 inches 122 cm between the intake air and vent termination or any other appliance vent that discharges moisture laden air such as clothes dryers This will reduce possibility of frost over fr...

Страница 28: ...rmination s is still pointing down towards the ground See Figure 26 16 Return to Power Vent Installation page 23 or Direct Vent Installation page 24 to complete the installation of the intake air and...

Страница 29: ...posed of AL29 4C must not mix parts from the different manufacturers The joints of these products are sealed by internal gaskets Do not use any other type of sealant When assembling these vent systems...

Страница 30: ...on page 25 5 When installing a concentric termination through a sidewall ensure that all exterior sidewall clearance requirements for the termination shown in Figure 52 page 38 are being maintained Th...

Страница 31: ...age cracking of the vent cap and or vent pipe 7 Install the vent cap vent pipe assembly into the intake air Y fitting assembly Ensure the small diameter vent pipe is cemented and bottomed in the Y fit...

Страница 32: ...clearances separation between terminations are maintained Ensure multiple terminations are arranged or grouped as required Note These clearances must be maintained to prevent the recirculation of vent...

Страница 33: ...on on clearances See Figure 32 page 32 when installing three concentric terminations SIDEWALL ROOF Figure 36 Two Concentric Terminations Side Wall And Roof Four Concentric Terminations Four concentric...

Страница 34: ...e solvent cementing procedures outlined in the IPEX System 636 Installation Guide which is available on the web www ipexinc com 3 To fasten the base to the wall use the supplied screws and anchors A 3...

Страница 35: ...ke Moisture Protection Figure 45 Direct Vent Horizontal Enlarged View of Direct Vent Air Intake Moisture Protection Figure 46 Direct Vent Vertical Vent Horizontal Intake Enlarged View of Direct Vent A...

Страница 36: ...d View of Direct Vent Air Intake Moisture Protection Figure 49 Direct Vent Horizontal Concentric Enlarged View of Direct Vent Air Intake Moisture Protection Figure 50 Direct Vent Horizontal Low Profil...

Страница 37: ...nto building or combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appli ances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appli ances 1...

Страница 38: ...nto building or combustion air inlet to any other appliance 6 in 15 cm for appli ances 10 000 Btuh 3 kW 12 in 30 cm for appli ances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appli ances...

Страница 39: ...hese instructions and local building codes Field supplied materials required for installation include Approved PVC cement and PVC primer 1 2 inch PVC pipe minimum length to equal the distance between...

Страница 40: ...RAP Figure 54 Supply Gas Line Installation Ensure all gas pipe is clean on the inside before installation To trap any dirt or foreign material in the gas supply line a sediment trap must be installed...

Страница 41: ...pply system perform a leak test to avoid the possibility of fire or explosion Fire and Explosion Hazard Leak test gas connections before placing water heater in operation Disconnect gas piping at main...

Страница 42: ...wire from the power supply must connect to the black jumper wire or the L1 terminal block location in the junction box and the 120 VAC neutral wire must connect to the white jumper wire or the Neutral...

Страница 43: ...age 15 4 Thermal Expansion and Closed Water Systems page 14 5 For multiple water heater installations see Water Piping Diagrams page 69 WATER PIPING DIAGRAMS This manual provides detailed water piping...

Страница 44: ...ter Never leave a child or disabled person unattended in a bathtub or shower The water heater should be located in an area where the general public does not have access to set temperatures Setting the...

Страница 45: ...on of the various operational states The Desktop screen also displays animated Status Icons to convey operational information see Table 18 page 46 for descriptions of the Status Icons The water heater...

Страница 46: ...Display will read Status Water Heating Disabled For more information see Enable Disable Circuit page 42 The Combustion Blower is being energized The Spark Igniter is being energized See Figure 2 page...

Страница 47: ...eater must be cycled off and on at the breaker to reset the control system NOTE Cycling power will not reset the control system if the condition that caused the Fault has not been corrected CONTROL SY...

Страница 48: ...tem Note Higher Temperature settings increase wear and operating costs Set the Operating Set Point to the lowest setting which produces an acceptable hot water supply This will always provide the most...

Страница 49: ...fferential 8 F Tank Temperature 120 F Tank Probe Offset 0 F HEATER STATUS MENU Description Action Display Press Heater Status from the Main Menu to enter this menu This menu contains non adjustable op...

Страница 50: ...module Use External Enable Enables Disables the external enable circuit External Enable Status Displays whether or not the external enable circuit has been activated Ignition Trials Displays the numb...

Страница 51: ...The newest event will replace the oldest Faults will clear after 30 days Press the Fault to view details for each Fault or Alert message stored Fault History HELP BACK 1 Upper Temp Probe Open 47 0 day...

Страница 52: ...e setting from No to Yes and press ACCEPT to save the new setting Note The Access Code at the bottom of the Service Contact Information screen is for manufacturing engineering purposes only There are...

Страница 53: ...ot water faucet opened in Step 2 as water starts to flow INITIAL START UP REQUIRED TEST EQUIPMENT One U tube manometer recommended ranges 0 14 W C 0 3 5 kPa and 0 35 W C 0 8 7 kPa or pressure gauges O...

Страница 54: ...h t e h t t e S o t s e t u n i m 5 e v i f t i a W s a g y n a t u o r a e l c s a g l l e m s n e h t u o y f I n i B w o l l o F P O T S u o y f I l e b a l s i h t n o e v o b a n o i t a m r o f...

Страница 55: ...water heater s share a common gas supply main with other gas fired appliances the supply gas pressures shall be measured at each water heater with all gas fired appliances connected to a common main f...

Страница 56: ...ge the Operating Set Point to the lowest temperature setting see Operating Set Point and Differential Adjustment page 48 2 When the water heater has completed its shut down sequence and enters the sta...

Страница 57: ...and repeat the operating cycle TROUBLESHOOTING INSTALLATION CHECKLIST The list below represents some of the most critical installation requirements that when overlooked often result in operational pr...

Страница 58: ...fferential setting a heating cycle is activated Spark Ignition Transformer is energized 24 Volt Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monito...

Страница 59: ...r see instructions in Checking The Firing Rate page 56 Note The water heaters covered by this manual are capable of modulating their firing rate The firing rate is dictated by the hot water draw and v...

Страница 60: ...se rumbling and pounding noises during heating cycles See Maintenance page 63 for sediment and lime scale removal procedures Normal operating noise of electrical components Combustion Blower transform...

Страница 61: ...a manometer ensure the supply gas pressure is above minimum pressure requirement listed on heater s data plate before and during operation Ensure wire connections to gas pressure switch are clean and...

Страница 62: ...e Advanced button for Ensure wire connections to upper temperature probe are clean and tight Using a thermometer check the water temperature of the heater Use a multi meter and check for continuity be...

Страница 63: ...move sediment and allow the water to flow until it runs clean 9 Close the water heater drain valve when flushing is completed 10 Remove the drain hose 11 Fill the water heater see Filling The Water He...

Страница 64: ...checking the Temperature Pressure Relief Valve operation make sure that 1 no one is in front of or around the outlet of the Temperature Pressure Relief Valve discharge line and 2 that the water discha...

Страница 65: ...y operating the valve it fails to completely reset and continues to release water immediately close the cold water inlet to the water heater and drain the water heater see Draining And Flushing page 6...

Страница 66: ...LAYOUT 11 12 1 J16 J5 J3 J13 J4 J17 J10 J9 J14 J15 J1 J6 J12 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 6 6 6 6 6 6 7 7 8 8 8 9 9 7 10 8 F...

Страница 67: ...67 WIRING DIAGRAM Figure 67 Wiring Diagram...

Страница 68: ...0 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION FIELD SUPP...

Страница 69: ...N ONE WATER HEATER SINGLE TEMPERATURE WITH BUILDING RECIRCULATION NOTES 1 Preferred piping method 2 The temperature and pressure relief valve setting shall not exceed pressure rating of any component...

Страница 70: ...WITH BUILDING RECIRCULATION NOTES 1 Preferred piping method 2 The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system 3 Service valves are sho...

Страница 71: ...exceed pressure rating of any component in the system 3 Service valves are shown for servicing unit However local codes shall govern their usage 4 The tank temperature control should be wired to and...

Страница 72: ...stat should be set 5 degrees F higher than the tank temperature control LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TEMPERATURE CONTROL PROBE DRAIN FULL PORT BALL V...

Страница 73: ...E CIRCULATING PUMP TEMPERATURE CONTROL PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK...

Страница 74: ...ING PUMP TEMPERATURE CONTROL PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCA...

Страница 75: ...he temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system 3 Service valves are shown for servicing unit However local codes shall govern their us...

Страница 76: ...d by improper gas supply line sizing gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Abuse misuse acciden...

Страница 77: ...77 NOTES...

Страница 78: ...78 NOTES...

Страница 79: ...79 NOTES...

Страница 80: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 365 0024 Parts 800 821 2017 www statewaterheaters com Copyright 2018 State Water Heaters All rights reserved...

Отзывы: