7
Servicing should only be performed by a Qualified Service Technician
GAS PIPING
Contact your local gas service company to ensure that adequate gas service is available and to review
applicable installation codes for your area.
Size the main gas line in accordance with Table below. The figures shown are for straight lengths of pipe
at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as
elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the latest version of the
National Fuel Gas Code.
Schedule 40 Steel or Wrought Iron Pipe is the preferred material for the gas line of this water heater. It
is imperative to follow the sizing recommendations in the latest version of the National Fuel Gas Code if
Corrugated Stainless Steel Tubing (CSST) is used as the gas line for this water heater.
The heater is not intended for operation at higher than 14.0" W.C.- natural gas, (1/2 pound per square inch
gage) supply gas pressure. Exposure to higher supply pressure may cause damage to the gas valve which
could result in fire or explosion. If overpressure has occurred such as through improper testing of gas lines or
emergency malfunction of the supply system, the gas valve must be checked for safe operation. Make sure
that the outside vents on the supply regulators and the safety vent valves are protected against blockage.
These are parts of the gas supply system, not the heater. Vent blockage may occur during ice storms.
GAS SUPPLY PIPE LENGTHS (IN FEET)
Maximum Equivalent Pipe Length - Natural Gas Only
Input rate
(BTU/HR)
Schedule 40 Steel or Wrought Iron Pipe
1/2"
3/4"
1"
1 1/4"
1 1/2"
120,000
20
70
200
200
200
154,000
10
40
150
200
200
180,000
-
30
100
200
200
199,000
-
30
90
200
200
250,000
-
20
60
200
200
275,000
-
10
50
200
200
310,000
-
10
40
150
200
366,000
-
-
30
100
200
390,000
-
-
20
100
200
Fitting Type*
Equivalent length in feet
45°Ell
0.7
1.0
1.2
1.6
1.9
90°Ell
1.6
2.1
2.6
3.5
4.0
Tee
3.1
4.1
5.2
6.9
8.0
Natural Gas 0.60 Specific Gravity, 0.50" W.C. Pressure Drop
*Screwed Fittings
It is important to guard against gas valve fouling from contaminants in gas ways. Such fouling may cause
improper operation, fire or explosion.
If copper supply lines are used they must be internally tinned and certified for gas service. Before attaching
the gas line, be sure that all gas pipe is clean on the inside. The instructions in this section on venting must
be followed to avoid choked combustion or recirculation of flue gases. Such conditions cause sooting or risks
of fire and asphyxiation.
Содержание SBD100390E
Страница 14: ...13 Servicing should only be performed by a Qualified Service Technician SEQUENCE OF OPERATION FLOW CHART...
Страница 28: ...27 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM 118 119 SERIES CONTROLS...
Страница 29: ...28 Servicing should only be performed by a Qualified Service Technician NOTES...
Страница 30: ...29 Servicing should only be performed by a Qualified Service Technician NOTES...