Servicing should only be performed by a Qualified Service Technician
STEP 9: IID MODULE TEST
CONDITION:
•
Pilot Flame Noted, No Sparking, No Main Burner.
Using a multimeter, test for 24 VAC between terminal MV on the IID and 24V (GND).
IF
THEN
24 VAC is not present:
•
Replace the IID module. Check the gas valve
before applying power to replacement module.
24 VAC is present:
•
Check the gas valve.