background image

18

DIAGNOSTIC CODES 

DISPLAY SHOWS

INDICATES

CORRECTIVE ACTION

UPPER ELEMENT  

CONNECT  

FAULT

1.  Upper element is not 

functioning

1.  Turn off power at the circuit breaker/fuse box and check for 

a loose connection at the element. For access directions 

see “Heating Element Replacement” section. If error persists 

proceed to the next step.

2.  Replace non-functioning element. See “Heating Element 

Replacement” section.

LOWER ELEMENT  

CONNECT  

FAULT

1.  Lower element is not 

functioning

1.  Turn off power at the circuit breaker/fuse box and check for 

a loose connection at the element. For access directions 

see “Heating Element Replacement” section. If error persists 

proceed to the next step.

2.  Replace 

non-functioning

 element. See “Heating Element 

Replacement” section.  

IMPORTANT:

 Using an element greater than 2000 watts in 

place of the lower element will damage the water heater and 

void the warranty.

HEAT PUMP  

CONNECT  

FAULT

1.  Heat Pump compressor is 

not functioning. 

1.  Contact a qualified person to service the heat pump.

FAN  

CONNECT  

FAULT

1.  Heat Pump fan is not 

functioning. 

1.  Contact a qualified person to service the unit. 

AMBIENT TEMP 

SENSOR SHORT OR 

OPEN

OR AD ERROR

1.  Ambient Temperature 

Sensor is not functioning.

1.  Contact a qualified person to service the unit.

UPPER TEMP

SENSOR SHORT OR 

OPEN

OR AD ERROR

1.  Upper Temperature Sensor 

is not functioning.

1.  Contact a qualified person to service the unit.

LOWER TEMP

SENSOR SHORT OR 

OPEN

OR AD ERROR

1.  Lower Temperature Sensor 

is not functioning.

1.  Contact a qualified person to service the unit.

DISCHARGE TEMP

SENSOR SHORT OR 

OPEN

OR AD ERROR

1.  Discharge Temperature 

Sensor is not functioning.

1.  Contact a qualified person to service the unit.

COIL TEMP

SENSOR FAULT

OR AD ERROR

1.  Coil Temperature Sensor is 

not functioning.

1.  Contact a qualified person to service the unit.

MAIN CIRCUIT BOARD  

FAULT

1.  Main Circuit Board is not 

functioning.

1.  Contact a qualified person to service the unit.

HIGH TEMP

LOCKOUT

1.  Water temperature in unit 

has exceeded 190° F.

1.  See “Safety Shut-off” section.

CONDENSATE  

DRAIN  

ALARM

 

(If Accessory Condensate 

Pump is Installed)

1.  Condensate pump failure.

1.  Check to see if accessory condensate pump is plugged in and 

has power. Also check circuit breaker/fuse box and GFCI (if 

used).  if error persists proceed to the next step.

2.  Check condensate pump outlet tube for blockage. if error persists 

proceed to the next step.

3.  Check control wire connections to condensate pump. If error 

persists proceed to the next step.

4.  Replace accessory condensate pump. If error persists contact a 

Qualified Person.

LOW WATER 

LEVEL ALARM

1.  Not enough water in the 

tank.  

(Tank not full)

1.  Fill Completely - Open all hot water taps in home and run until 

water (uninterrrupted by air) flows from all open hot water 

taps.

COMMUNICATION

ERROR

1.  No communication between 

mainboard and user 

interface board.

1.  Contact a qualified person to service the unit.

Содержание Premier

Страница 1: ...ur Water Heater 3 9 Consumer Information 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Confined Space Installation 5 6 Water System Piping 7 8 Temperature Pressure Relief Valve 9 10 Electrical Requirements 10 11 Installation Checklist 12 Operating Your Water Heater 13 15 Before Using 13 Water Temperature Regulation 13 Adjusting the User Interface Module Operation...

Страница 2: ...s extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system When hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or...

Страница 3: ...le to include the model and serial number Retain your original receipt as proof of purchase Basic Operation Fundamentals The Heat Pump Water Heater HPWH is an integrated heat pump water heater unit having an 850 watt compressor and external coil heat exchanger with backup electric elements See Figure 1 When in Efficiency Mode the heat pump draws heat from the ambient air in the room and transfers ...

Страница 4: ...n Select a location near the center of the water piping system The unit must be installed indoors and in a vertical position on a level surface The flooring beneath the water heater must be able to support the weight of the water heater when filled with water See Table 1 IMPORTANT The water heater must have unresticted airflow and requires a minimum installation space of 750 cubic feet As an examp...

Страница 5: ... the building structure through one or more louvered grills or through a fully louvered door leading into the confined space The alternate location from where inlet air will be derived must provide a minimum of 750 cubic feet of space when using this installation method When the Outlet Duct Kit is installed outlet air from the unit is redirected to an alternate location The alternate location to w...

Страница 6: ...aightly as possible there must be no kinks or flattening of the ductwork 10 The Outlet Duct Kit and connected ductwork must redirect outlet air from the unit to a location other than the confined installation space The alternate location to where the outlet air is redirected must be a minimum of 750 cubic feet ITEM LOUVERED GRILL CONFINED SPACE CONFIGURATION door or wall MINIMUM SPACE cubic feet 6...

Страница 7: ...nce as shown in Figure 5 5 If installing the water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion 6 Install a shut off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 7 Install a d...

Страница 8: ...des Use appropriate primer and glue to cement the condensate drain lines to the heat pump drain pan NOTE The heat pump drain pan is ABS and the two condensate drain pipes should be PVC If a condensate pump is installed it should shut off the heat pump in the event the condensate pump fails or the float switch in the pump activates See Condensate Pump Installation section Closed System Thermal Expa...

Страница 9: ...lve and the end of the discharge line Shall terminate a maximum of six inches above a floor drain or external to the building In cold climates it is recommended that the discharge pipe be terminated at an adequate drain inside the building Shall be of material listed for hot water distribution Shall be installed to allow complete drainage of both the valve and discharge line Temperature Pressure R...

Страница 10: ... with water and all air is purged from the tank before making any electrical connections See Draining and Flushing Section 2 Turn off power to the electrical wiring for the water heater at the circuit breaker fuse box 3 Remove the left louvered access panel when facing the water heater by loosening the screws securing it to the water heater See figure 8 4 Loosen the screws securing the electrical ...

Страница 11: ...er 8 Press the power button to turn the water heater on and select the desired operational mode After about 8 minutes the heat pump will turn on 9 Test the operation of the shut off switch by unplugging the condensate pump and filling the condensate reservoir with water until the float switch opens the circuit 10 The heat pump should turn off and the error code CONDENSATE DRAIN ALARM will appear o...

Страница 12: ...ltered from freezing See Figure 5 All piping properly installed and free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section INSTALLATION CHECKLIST Mixing valve when applicable installed per manufacturer s instructions See Water Temperature Regulation section Condensate Drain L...

Страница 13: ...hing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature Regulation Water temperature over 125 F can cause severe burns instantly or death from scalds Children disabled and elderly are at highest risk of being scalded Feel water before bathing or showering Temperature limiting valves are availab...

Страница 14: ...duced recovery time This mode uses the heat pump as the primary heating source The heating element will heat water if demand exceeds a predetermined level so that the set point temperature can be recovered more quickly EFFICIENCY Efficiency Mode Is the most energy efficient mode This mode uses the heat pump to heat water in the tank The elements are not used unless the ambient operating temperatur...

Страница 15: ...r heater sounds or noises may be heard These noises are common and may result from the following 1 Normal expansion and contraction of metal parts during periods of heat up and cool down 2 Sediment buildup on or around the elements could create varying amounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section 3 The heat pump ...

Страница 16: ...PORTANT Do not turn on power to the water heater unless it is completely filled with water To ensure that the tank is full open a hot water faucet and allow the water to run until the air is purged and the water flows uninterrupted from the faucet 8 Press the power button to turn the water heater on NOTE The water heater will conduct a system diagnostic prior to operation If the water heater is go...

Страница 17: ...Air Filter Remove and inspect clean if needed and reinstall Condensate drain pan and condensate lines The lower metal drain pan for standing water which may indicate a clogged condensate drain pan condensate lines or plumbing leak Leaking or damaged water piping Presence of corrosive materials in the installation area Presence of combustible materials near the water heater After servicing this wat...

Страница 18: ...g 1 Contact a qualified person to service the unit LOWER TEMP SENSOR SHORT OR OPEN OR AD ERROR 1 Lower Temperature Sensor is not functioning 1 Contact a qualified person to service the unit DISCHARGE TEMP SENSOR SHORT OR OPEN OR AD ERROR 1 Discharge Temperature Sensor is not functioning 1 Contact a qualified person to service the unit COIL TEMP SENSOR FAULT OR AD ERROR 1 Coil Temperature Sensor is...

Страница 19: ...8 Drain and flush tank Water conditioning may be necessary to minimize build up HIGH OPERATION COSTS 1 Temperature set point too high 2 Air filter dirty 3 Electric mode selected 4 Water connections to unit reversed 5 Heat lost thru long run of exposed pipe 6 Hot water leak at faucet or piping 7 Sediment or scale build up in tank 1 Decrease set point temperature see Adjusting the User Interface Mod...

Страница 20: ... Valve 15 Element Terminal Cover 16 ECO Cover 17 Control Board 18 Compressor ECO Relay 19 EPS Cover 20 Ambient Coil Discharge Temperature Sensor 21 Upper Lower Tank Temperature Sensor 22 Run Capacitor 23 Control Board Module Fuses REPAIR PARTS Repair parts may be ordered through your plumber local distributor home improvement center or by calling 1 800 527 1953 When ordering repair parts always gi...

Страница 21: ...21 NOTES ...

Страница 22: ...22 Copyright 2012 State Industries Inc All rights reserved ...

Отзывы: