Startco Engineering Ltd.

Page 1

SE-701 Ground-Fault Monitor

 

Rev. 5

Pub. SE-701-M, December 14, 2006.

1.  G

ENERAL

The SE-701 is a microprocessor-based ground-fault

monitor for resistance-grounded and solidly grounded
systems.  Its output relay can operate in the fail-safe or
non-fail-safe mode for undervoltage or shunt-trip
applications.  The normally open and normally closed
output contacts are isolated for use in independent control
circuits.  Additional features include LED and
fluorescent-flag trip indication, autoreset or latching trips
with front-panel and remote reset, self test, 0- to 5-V
analog output, inputs for standard and sensitive
ground-fault current transformers, CT verification for
sensitive current transformers, digital selector switches,
switch-selectable algorithms for fixed-frequency or
variable-frequency applications, and an inhibit that can be
enabled to prevent the output relay from operating during
a high-current ground fault.

Ground-fault current is sensed by a standard CT with a

1-A or 5-A secondary, or by a sensitive CT with a
5-A-primary rating (EFCT-1, EFCT-2, or EFCT-26).  The
trip level of the ground-fault circuit is switch selectable in
1% increments from 1 to 99% of the CT-primary rating.
Trip time is switch selectable with 10 settings from 0.05
to 2.5 seconds.

2.  O

PERATION

2.1  C

ONFIGURATION

-S

WITCH

 S

ETTINGS

See Fig. 1 for switch configuration.

2.1.1  R

ELAY

 O

PERATING

 M

ODE

The SE-701 has one output relay with isolated

normally open and normally closed contacts.  Switch 1 is
used to set the operating mode of the output relay.  In the
fail-safe mode, the output relay energizes when the
ground-fault circuit is not tripped.  In the non-fail-safe
mode, the output relay energizes when a ground-fault trip
occurs.

2.1.2  I

NHIBIT

Switch 2 is used to select Class I or Class II operation.

In the INHIBIT OFF position, high-current inhibit is off
for Class I operation.  In the INHIBIT ON position, high-
current inhibit is on for Class II operation.  If high-current
inhibit is on and ground-fault current escalates above
eleven times the CT-primary rating before the ground-
fault circuit trips, the output relay will not operate until
ground-fault current falls below eight times the
CT-primary rating.  This feature allows the overcurrent
protection to operate in applications where the ground-
fault current can be larger than the interrupting capacity
of the device tripped by the SE-701.

2.1.3  CT V

ERIFICATION

Switch 3 is used to enable CT verification with an

EFCT-series CT.  In the CT VERIFY ON position, a trip
will occur if the CT is disconnected.  The red TRIP LED
will flash to indicate a trip initiated by a CT fault.  Switch
3 must be in the CT VERIFY OFF position when a 5-A-
or 1-A-secondary CT is used.

2.1.4  F

ILTER

 S

ELECTION

Switch 4 is used to select the filtering algorithm for a

fixed-frequency (50/60 Hz) or variable-frequency
application.  The fixed-frequency algorithm allows lower
trip levels to be used by rejecting harmonics that can
cause nuisance tripping.  The fixed-frequency setting can
be used in an application on the line side of a variable-
frequency drive.  The variable-frequency setting should
be used if the CT is located on the load side of a variable-
frequency drive.

2.1.5  A

UTORESET

Switch 5 is used to select autoreset or latching trips.

See Section 2.2.3.

2.2  F

RONT

-P

ANEL

 C

ONTROLS

2.2.1  G

ROUND

-F

AULT

 T

RIP

 L

EVEL

The % CT PRIMARY selector switches are used to set

the ground-fault trip level as a percentage of the
CT-primary rating.  Protection against arcing ground
faults in a solidly grounded system requires a ground-
fault CT that will not saturate below the operating value
of the overcurrent protection.  For reliable ground-fault
detection, the ground-fault trip level must be substantially
below the prospective ground-fault current.  To avoid
sympathetic tripping, the trip level must be above the
charging current of the largest feeder; and to eliminate
nuisance tripping, surge current must not saturate the CT.
For CT-selection assistance, see Technical Information
11.1 available at www.startco.ca.

2.2.2  G

ROUND

-F

AULT

 T

RIP

 T

IME

The TIME (s) selector switch is used to set the ground-

fault trip delay time for coordination with upstream and
downstream ground-fault devices.  Coordination requires
the same trip level for all ground-fault devices in a system
and the trip time to progressively increase upstream.  The
amount of equipment removed from the system will be a
minimum if the first ground-fault device to operate is the
one immediately upstream from the fault.

2.2.3  R

ESET

The reset circuit responds only to a momentary closure

so that a jammed or shorted switch will not prevent a trip.
The front-panel RESET switch is inoperative when the
remote-reset terminals (6 and 7) are shorted.

Содержание SE-701

Страница 1: ...SE 701 MANUAL GROUND FAULT MONITOR December 14 2006 Revision 5 Copyright 2006 by Startco Engineering Ltd All rights reserved Publication SE 701 M Document S95 C701 00000 Printed in Canada ...

Страница 2: ...rip 3 2 3 3 Inhibit 3 2 4 Analog Output 3 3 Installation 3 4 Technical Specifications 8 5 Ordering Information 9 6 Warranty 9 7 Ground Fault Performance Test 10 LIST OF FIGURES PAGE 1 SE 701 Outline and Mounting Details 2 2 Typical Connection Diagram 3 3 EFCT 1 Outline and Mounting Details 4 4 EFCT 2 Outline and Mounting Details 5 5 EFCT 26 Outline and Mounting Details 6 6 PMA 55 Panel Mount Adapt...

Страница 3: ...operate in applications where the ground fault current can be larger than the interrupting capacity of the device tripped by the SE 701 2 1 3 CT VERIFICATION Switch 3 is used to enable CT verification with an EFCT series CT In the CT VERIFY ON position a trip will occur if the CT is disconnected The red TRIP LED will flash to indicate a trip initiated by a CT fault Switch 3 must be in the CT VERIF...

Страница 4: ...Startco Engineering Ltd Page 2 SE 701 Ground Fault Monitor Rev 4 Pub SE 701 M December 14 2006 FIGURE 1 SE 701 Outline and Mounting Details ...

Страница 5: ... INHB LED s will be ON Inhibit indication is reset when the ground fault trip is reset Inhibit operation and indication will not respond if Switch 2 is in the INHIBIT OFF position 2 4 ANALOG OUTPUT The non isolated 0 to 5 V analog output indicates ground fault current sensed by the ground fault CT The output is 5 V at 100 of the CT primary rating 3 INSTALLATION An SE 701 can be surface or DIN Rail...

Страница 6: ...0 121 0 80 0 30 0 20 5 30 0 138 0 MAX 126 0 56 0 46 0 4 76 0 98 4 33 0 22 0 22 0 87 3 23 2 75 2 21 4 76 3 15 1 18 0 81 1 18 5 43 4 96 2 21 1 81 M5 SCREWS TOP MOUNTING DETAIL NOTE 2 FRONT SIDE 5 0 0 20 0 FLUX CONDITIONER OPTIONAL RECESSED FOR 8 mm HEX NUT 1 0 0 04 DEEP EFCT 1 EARTH FAULT CT 600 V INSULATION CLASS STARTCO E N G I N E E R I N G L T D P P S S 2 2 1 1 FIGURE 3 EFCT 1 Outline and Mounti...

Страница 7: ... 0 33 2 06 2 36 2 52 1 22 9 29 M5 SCREWS TOP MOUNTING DETAIL M4 OR 8 32 TAP SIDE FRONT E F C T 2 E A R T H F A U L T C T 6 0 0 V I N S U L A T I O N C L A S S S T A R T C O E N G I N E E R I N G L T D 5 0 0 20 DIA NOTES 1 DIMENSIONS IN MILLIMETRES INCHES MOUNTING SCREWS M4 OR 8 32 2 P P S S2 2 1 1 S P 1 1 139 7 5 50 BONDING SCREW FLUX CONDITIONER INCLUDED 26 5 1 04 FIGURE 4 EFCT 2 Outline and Moun...

Страница 8: ...NTING SCREWS M4 OR 8 32 68 0 26 0 52 5 5 0 5 0 68 0 34 0 26 5 25 0 58 0 17 0 26 5 72 0 34 0 7 0 110 0 MAX 52 5 42 6 2 68 1 02 2 07 0 20 0 20 2 68 1 34 1 04 0 98 2 28 0 67 1 04 2 83 1 34 0 87 0 43 2 07 1 68 M5 SCREWS TOP MOUNTING DETAIL M4 OR 8 32 TAP FRONT SIDE 4 0 0 16 0 RECESSED FOR 7 mm HEX NUT 3 0 0 12 DEEP P P S S 2 2 1 1 EFCT 26 EARTH FAULT CT 600 V INSULATION CLASS STARTCO E N G I N E E R I...

Страница 9: ...Startco Engineering Ltd Page 7 SE 701 Ground Fault Monitor Rev 5 Pub SE 701 M December 14 2006 FIGURE 6 PMA 55 Panel Mount Adapter ...

Страница 10: ... On Class II Level 11 x CT Primary Rating Input Algorithms DFT Digital or Peak Digital Filter 50 to 60 Hz Bandpass CT 1 or 5 A Secondary Rating or EFCT x CT Detection Open Circuit Detection with EFCT x Thermal Withstand Continuous 5 x CT Secondary Rating 1 Second 80 x CT Secondary Rating Burden 5 A input 0 01 Ω 1 A input 0 05 Ω EFCT input 2 Ω Analog Output Range 0 to 5 Vdc 5 V 100 CT Rating Output...

Страница 11: ...y rating 82 mm 3 2 window EFCT 1FC Flux Conditioner for EFCT 1 70 mm 2 7 window EFCT 2 Sensitive Earth Fault CT with Flux Conditioner 5 A primary rating 139 mm 5 5 window EFCT 26 Sensitive Earth Fault CT 5 A primary rating 26 mm 1 window PMA 55 Panel Mount Adapter SE EFVC Voltage Clamp Consult factory for custom mounting adapters 6 WARRANTY The SE 701 Ground Fault Monitor is warranted to be free f...

Страница 12: ...determine the existence of alternate ground paths d Verify proper reaction of the circuit interrupting device in response to a simulated or controlled ground fault current To simulate ground fault current use CT primary current injection Fig 7 a shows a test circuit using a Startco SE 400 Ground Fault Relay Test Unit The SE 400 has a programmable output of 0 5 to 9 9 A for a duration of 0 1 to 9 9...

Отзывы: