background image

OPERATION PROCEDURES

Daily Start-Up Procedures

1. Set the On/Off switch to the off position.

2. Check the air compressor visually for any damage or obstruction.

3. Close the drain valve.

4. Plug the power cord into the proper receptacle.

5. Turn the On/Off switch to the On position and the compressor should start and build air pressure in the tank to cut-out

pressure and then shut off automatically.

6. Adjust the regulator to a PSI setting that is recommended for your application.

7. The air compressor is now ready for use.

WARNING

Improper installation of the grounding plug can result in a risk of electric shock. If repair or

replacement of the cord or plug is necessary, do not connect the grounding wire to either flat blade terminal. The wire

with insulation having an outer surface that is green with or without yellow stripes is the grounding wire. Check with a

qualified electrician or serviceman if the grounding instructions are not completely understood, or if in doubt as to

whether the product is properly grounded. Do not modify the plug provided; if it will not fit the outlet, have the proper

outlet installed by a qualified electrician.

Daily Shut-Down Procedures

1. Set the Auto-On/Off lever to the Off position.

2. Unplug the power cord from the receptacle.

3. Set the outlet pressure to zero on the regulator.

4. Remove any air tools or accessories.

5. Open the drain valve allowing air to bleed from the tank. After all of the air has bled from the tank, close the drain

valve to prevent debris buildup in the valve.

Water that remains in the tank during storage will corrode and weaken the air tank, which could cause the tank to

rupture. To avoid serious injury, be sure to drain the tank after each use or daily.

CAUTION

When draining the tank, always use ear and eye protection. Drain the tank in a suitable location;

condensation will be present in most cases of draining.

MAINTENANCE

NOTE:

Qualified service personnel should perform any service procedure not covered in the maintenance schedule

below.

ITEMS TO CHECK/CHANGE

Before Each

Use or Daily

After First Ten

Hours

Every 100

Hours

Check Tank Safety Valve

X

Overall Unit Visual Check

X

Check Air Filter (more frequently in dusty orhumid environments)

X

CAUTION

To ensure efficient operation and longer life of the air compressor unit, a routine maintenance

schedule should be followed. The following schedule is geared toward a consumer whose compressor is used in a

normal working environment on a daily basis. If necessary, the schedule should be modified to suit the condition under

which your compressor is used. The modifications will depend upon the hours of operation and the working

environment. Air compressors used in an extremely dirty and/or hostile environment will require a greater frequency of

all maintenance checks.

Содержание 65168

Страница 1: ... KEEP THIS MANUAL FOR SAFETY WARNINGS PRECAUTIONS ASSEMBLY FOR QUESTIONS PLEASE CALL CUSTOMER SERVICE 909 628 4900 SERIAL NUMBER ON THE BACK OF THE MANUAL OR THE MONTH AND VEAR OF PURCHASE IF OPERATION INSPECTION MAINTENANCE AND CLEANING PROCEDURES WRITE THE PRODUCT S PRODUCT HAS NO SERIAL NUMBER ...

Страница 2: ... Turn off the air compressor and drain the air tank before performing any type of maintenance or disassembly of the hoses or fittings Never point any nozzle or sprayer toward any part of the body or at other people or animals Risk to Breathing Avoid using the air compressor in confined areas Always have adequate space 30 cm on all sides of the air compressor Also keep children pets and others out ...

Страница 3: ...on and performance Location of the Air Compressor The air compressor should always be located in a clean dry and well ventilated environment The unit should have at minimum 30cm of space on each side The air filter intake should be free of any debris or obstructions Check the air filter on a daily basis to be sure it is clean and in working order Extension Cords Use only a 3 wire extension cord th...

Страница 4: ...to zero on the regulator 4 Remove any air tools or accessories 5 Open the drain valve allowing air to bleed from the tank After all of the air has bled from the tank close the drain valve to prevent debris buildup in the valve Water that remains in the tank during storage will corrode and weaken the air tank which could cause the tank to rupture To avoid serious injury be sure to drain the tank af...

Страница 5: ... leak remains contact a service technician Air leak from safety valve Operate the safety valve manually by pulling on the ring If the valve continues to leak when in the closed position it should be replaced Pressure reading on the regulated pressure gauge drops when an accessory is used If there is an excessive amount of pressure drop when the accessory is used replace the regulator NOTE Adjust t...

Страница 6: ......

Страница 7: ...01 1 48 SCREW M6X20 2 14 BEARING 6201 1 49 5 15 BEARING 6203 1 50 3 16 5 3 ij 1 51 SPRING WASHER M6 3 17 ECCENTRIC 1 52 3 18 BELT 1 53 SCREW M5X12 8 19 SCREW M6X16 1 54 RUBBER FOOT 4 20 COVER OF CONROD 1 55 DRAIN VALVE 1 21 PISTON RING 1 56 HANDLE 1 22 CONROD 1 57 SHROUD 1 23 SCREW M4X20 1 58 TAPPING SCREW ST4X12 2 24 SPRING WASHER M4 1 59 PRESS FIXTURE 1 25 NUT M4 1 60 POWER SWITCH 1 26 ROUND FAN ...

Страница 8: ...erial Number Here __________________ Note If product has no serial number record month and year of purchase instead Note Some parts are listed and shown for illustration purposes only and are not available individually as replacement parts The material in this manual is for informational purposes only The product s it describesare subject to change without prior notice due to the manufacturer s co...

Отзывы: