Figure 19, K1200 Installation side view.
Figure 20, K1700/ 2300 Installation side view
•
Failure to comply with these requirements may prevent the correct operation of the stove. Follow all the instructions
presented on the diagrams.
The pellet stove stoves operate with the combustion chamber in vacuum, so it is necessary to have a fume exhaust pipe to
extract combustion gases properly.
All material used to flue the product must comply with current Building regulations.
Insulation:
The flue must be double-walled and insulated to make sure that flue gases do not cool down going outwards,
which would cause an inadequate circulation and condensation that may damage the stove.
Windproof terminal:
A windproof terminal must always be installed to avoid the backflow of flue gases.
Draught in the chimney
. All installation must guarantee a draught of 12 Pa (0.12mbars) measured when hot and at the maximum
power.
Ventilation:
The stove must have adequate air for combustion and the room must have adequate air for ventilation , adequate air supply must be
provided in line with building regulations. The boiler pellet stove has a circular pipe (
Æ
50mm) that may be connected to the exterior of
the house. An outside air kit and adaptor from 50-100 is available to order from Waterford Stanley.
This product should not be installed in the same room as an extractor fan. A spillage test should be undertaken where the
product is installed in a room adjacent to a room with an extractor fan.
7.3 Installation with a chimney
If the stove is to be installed in a chimney with a flue pipe of appropriate diameter direct to the stove. The chimney should be lined
with a 125mm flexible liner suitable for use with solid fuel.
A T-piece must be installed between the connection pipe and the 125mm flexi liner to allow for periodic inspection and annual
maintenance. The installation must be completed with a windproof cowl recommended for use with pellet stoves.
If you do not use the stove for a long time, check it to make sure that the flue pipes are clear before lighting the fire.
Dia.
125m
Dia.
100mm
Содержание K1700
Страница 2: ...2 ...
Страница 10: ...10 Figure 5 K1200 Connections Figure 6 K1700 Connections Figure 7 k2300 Connections ...
Страница 35: ...35 13 Exploded views K1200 ...
Страница 36: ...36 K1200 ...
Страница 38: ...38 K1700 ...
Страница 39: ...39 Exploded view K2300 ...
Страница 46: ...46 Figure53 Connection of pellet boiler using 2 way valves and automatic bypass Figure 54 ...