POSITION OF FAN FLUE TERMINAL FOR OIL FIRED COOKERS

OIL FIRED COOKERS

A

Directly below an opening, air brick, window etc..

600

B

Horizontally to an opening, air brick, window etc..

600

C

Below a gutter, eaves or balcony with protection

75

D

Below a gutter or a balcony without protection

600

E

From vertical sanitary pipework

300

F

From an internal or external corner

300

G

Above ground or balcony level

300

H

From a surface or boundary facing the terminal

600

J

From a terminal facing the terminal

1200

K

Vertically from a terminal on the same wall

1500

L

Horizontally from a terminal on the same wall

750

Refer to part of the Building Regulations England and Wales, Irish Building Regulations.  B.S. 5410 Part 1, and

Part F of the Building Standards (Scotland) Regulations.