The Stanley Alpha is a floor standing combined cooker
and central heating boiler. It gives independent operation
of space heating, domestic hot water and cooking.
The appliance is fired by two independent pressure jet oil
burners. Either burner can be independently operated.
The boiler is designed for use on a fully pumped, low
pressure hot water circulation system with a pumped over
run facility. It may be an open vented or alternatively a
sealed system limited to 3 bar.
IMPORTANT
z
This appliance must only be used with Kerosene
C2 to BS 2869.
z
An Indirect Cylinder to BS 1566: Part 1 must be
fitted.
z
If the heating circuits are controlled in such a way
that both heating and cylinder circuits can be
closed off at the same time then a BY-PASS LOOP
must be fitted.
z
An OFTEC approved Fire Valve MUST be fitted in
the oil supply line.
z
The supply in line filter MUST be fitted.
z
Permanent Ventilation must be provided.
THIS APPLIANCE IS A CONTROLLED SERVICE BY
DEFINITION AND REQUIRES EITHER FITMENT
UNDER THE REMIT OF BUILDING CONTROL OR
INSTALLATION BY AN OFTEC REGISTERED 105
TECHNICIAN (CLASSED AS COMPETENT PERSON)
WHO CAN SELF CERTIFY HIS OWN WORKS.
The appliance must be commissioned by a competent
engineer. Failure to install the appliance correctly could
lead to prosecution.
The installation of the appliance must be in accordance
with the relevant requirements of the current Building
Regulations in force and the bylaws of the local Water
Undertaking. It should also be in accordance with the
relevant current British Standard Codes of Practice.
BS5410
Installation of oil fired appliances for space
heating and hot water supply purposes. Part 1 Boiler of
rated output not exceeding 45kW.
BS5449
Central Heating for domestic purposes, Part 1.
Forced circulation hot water system.
Building Regulations England & Wales. Part J.
Heat producing appliances.
Building Standards Scotland
- Technical Standard Part
F. Heat producing appliances and storage of liquid and
gaseous fuel.
Building Regulations (Northern Ireland) Part L
- Heat
producing appliances.
The Control of Pollution (Oil) Regulations.
Location and Siting of the Appliance
To choose a location for the Stanley Alpha, the following
must be considered:
a. Satisfactory provision for installation of the flue.
b. A solid non-combustible hearth.
c. Sufficient space for installation.
d. Adequate space for combustion air vents (rear of
cooker).
e. Sufficient forward space must be available to allow the
right hand doors to be opened, in excess of 110° from
the closed position.
Hearth Construction
The hearth or base on which the appliance will stand must
be of sound construction, being able to bear the weight of
498Kg) the appliance. This must be of a non-combustible
material and must be level.
The location chosen for the appliance must permit the
installation and the provision of a satisfactory flue and an
adequate air supply. The location must also provide
adequate space for servicing and air circulation around
the appliance.
In addition, adequate clearance must be available at the
front of the appliance, to enable it to be operated and
serviced. Flues pipes and fittings must not be closer than
25mm to combustible materials and where passing
through a combustible partition such as ceiling or roof,
must be enclosed in a non-combustible sleeve providing
an air space of at least 25mm.
Space around the flue pipes passing through walls or
floors should be sealed against the passage of smoke
and flame, a fire stop must be provided where the flue
passes through a ceiling.
Where the cooker is to stand in a recess or against a wall
which is to be tiled, in no circumstances should the tiles
overlap the top plate.
The installation of the oil supply must be carried out in
accordance with current building regulations and OFTEC
recommendations.
It is the installers responsibility to correctly plan and size
the siting and fitting of the oil tank and run of pipework to
the appliance, ensuring that the oil tank is suitably sized
for the model of Stanley Alpha in use and that the oil
supply pipe is run correctly i.e. a two-pipe system
NOT A
DE-AERATION DEVICE
if the tank position is lower than
the appliance.
Site requirements
6
REGULATIONS
LOCATION
INTRODUCTION
OIL INSTALLATION
Содержание Alpha 120K
Страница 13: ...13 Site requirements FIG 6 External wiring with 2 zone valves ...
Страница 14: ...Site requirements 14 FIG 7 ...
Страница 22: ...22 FIG 16 ...
Страница 23: ...23 ...