Installation Instructions for 83KM/93KM–85KM/95KM IDH Max Cylindrical Locks

Components checklist

Special tools checklist

Field wiring for power connections between the lock 
and power supply or the lock and panel interface 
module.

If you’re powering the lock(s) through the panel 
interface module, calculate the total length of the 
power wire run by summing:

The distance from the power supply to the panel 
interface module.

The distance from the panel interface module to 
the first door.

If powering more than one door daisy-chained to 
the same power supply, add the total distance of 
the power runs between the doors.

If you’re powering the lock(s) using a separate power 
supply, calculate the total length of the power wire run 
by summing:

The distance from the power supply to the first 
door.

If powering more than one door daisy-chained to 
the same power supply, add the total distance of 
the power runs between the doors.

Refer to the table below to determine the minimum 
wire gauge based on the number of doors sharing the 
power supply and the total length of the wire run.

Field wiring for RS-485 communication connections 
between the lock and panel interface module 
(4000 feet maximum):
Category 5, shielded twisted pair; 24 AWG min.

Maximum wire length based on

no. of doors daisy-chained to power supply

Minimum

wire gauge

1 door

2 doors

3 doors

4 doors

250 feet

125 feet

75 feet

60 feet

18 AWG

400 feet

200 feet

130 feet

100 feet

16 AWG

600 feet

300 feet

185 feet

150 feet

14 AWG

Use the following checklist to make sure that you have the 
special tools necessary to install the components 
provided with your 83KM/93KM–85KM/95KM IDH Max 
Cylindrical Lock.

Three (3) to four (4) foot, 3/8

 drill bit

KD303 Drill jig

T20 TORX® bit driver (only used for security screw 
option)

† TORX is a registered trademark of the Camcar 

Division of Textron.

Содержание 83KM-93KM

Страница 1: ...sentative A panel interface module is provided with the lock The panel interface module receives token data and lock sensor data from the lock through an RS 485 connection It translates this data into...

Страница 2: ...requirements for ANSI BHMA 156 25 Side of door Range Inside 66 F to 74 F 19 C to 23 C Outside 31 F to 151 F 35 C to 66 C Side of door Range Inside and outside 32 F to 120 F 0 C to 49 C Use the follow...

Страница 3: ...distance from the power supply to the first door If powering more than one door daisy chained to the same power supply add the total distance of the power runs between the doors Refer to the table bel...

Страница 4: ...rk the vertical centerline of the door edge Note The recommended height from the floor to the centerline of the lock is 38 2 Fold the W16 Template Installation Template for 83KM 93KM IDH Max Cylindric...

Страница 5: ...HRB reader wire hole solenoid wire hole 3 8 diameter through door before drilling chassis hole chassis hole 2 1 8 diameter through door after drilling solenoid wire hole latch hole 1 diameter meets ch...

Страница 6: ...Drill a wire access hole through the frame side of the hinge mortise 2 Drill holes or pockets for the splice connectors in the frame and door Refer to the hinge manufacturer s specifications for the...

Страница 7: ...drill through bolt holes 9KW only 1 Press the drill jig KD303 onto the door engaging it with the latch tube prongs Make sure the front edge of the jig is parallel with the door edge 2 Drill the throu...

Страница 8: ...hole in the fire plate and into the hole drilled through the door to the hinge mortise 2 From the latch edge of the door fish the field wire harness through the door to the hinge mortise 3 Make sure t...

Страница 9: ...s out the wire hole to the inside of the door as shown in Figure 8 9 Install strike box and strike plate 1 In alignment with the center of the latchbolt mortise the door jamb to fit the strike box and...

Страница 10: ...r past the keeper 4 Slide the knob lever off of the sleeve Caution Be careful that you do not disconnect the lever keeper spring 11 Adjust for door thickness 1 Determine the door s thickness 2 Pull th...

Страница 11: ...chassis hole routing the solenoid wire through the notch Caution Make sure that the latch tube prongs engage the chassis frame and that the latch tailpiece engages the retractor 13 Install fire plate...

Страница 12: ...the chassis aligning the holes in the rose liner with the holes prepared in the door Caution Make sure that there is clearance for the solenoid wire between the RQE rose liner and the door 2 Install t...

Страница 13: ...chassis sleeve so it rests on the hub Note You do not need to change the positions of the DIP switches on the control electronics circuit board located in the inside escutcheon By default switches 1 t...

Страница 14: ...holes at the top and bottom of the fire plate 3 Tighten the mounting screw to the outside escutcheon until the fire plate and escutcheon are securely mounted to the door 4 Connect the reader wire har...

Страница 15: ...n making the sensor connections and solenoid connection make sure there are no loose wire connections where the wires are inserted into the connectors the connectors are firmly mated 18 Install bottom...

Страница 16: ...top cover above the fire plate and slide it down over the guide notches on the fire plate Caution Make sure that the top cover does not pinch any wires as you slide it over the fire plate 2 Use two co...

Страница 17: ...levers to check that they operate smoothly 21 Install core and throw member 1 Install the blocking plate onto the throw member Caution You must use the blocking plate to prevent unauthorized access F...

Страница 18: ...wires Install the wire transfer hinge 23 Install lock power supply optional If you are providing a separate power supply for the lock instead of providing power via the panel interface module connect...

Страница 19: ...l interface circuit board Note JP2 and JP3 shown in Figure 22a are used for manufacturing purposes only 3 Connect the RS 485 shield wire to one of the GND terminals on J1 26 Connect panel interface mo...

Страница 20: ...put Switch like output to the access control panel reader interface that indicates the status of the lock s RQE switch By default the output is closed to indicate the RQE switch is closed Note The loc...

Страница 21: ...ovided to the Reader LED input and the Sounder input must be greater than 3 5 volts DC to be interpreted as a 5 volts DC signal Signals with voltage less than 0 8 volts DC are interpreted as 0 volts D...

Страница 22: ...cuit board both must be set to ON automatic baud rate detection 38400 bps Switch 2 OFF Switch 3 OFF 19200 bps Switch 2 ON Switch 3 OFF 9600 bps Switch 2 OFF Switch 3 ON 2400 bps Switch 2 ON Switch 3 O...

Страница 23: ...that the red reader LED green reader LED and sounder respond as expected The lock should allow access verifying that the solenoid is working To check that the reader is working view the lock s event...

Страница 24: ...ate detection or to the same positions as DIP switches 2 and 3 on the panel interface circuit board Check the connections for all communication field wiring Check the communication connections between...

Отзывы: