Installation 

1. Check the following before beginning installation. 

Insulation resistance measurement: 

With the motor and cable (excluding the power supply cable) immersed in water, use a Megger to measure the insulation 

resistance between ground and each phase of the motor, and again between each phase of the motor. The Megger should 

indicate an insulation resistance of not less than 20mega ohms. While making the measurement, keep the power supply  

cable off the ground. 

 

We recommend that an auxiliary pump be kept on hand in case of emergency. 

 

2. Installation 

1. 

! WARNING: 

Under no circumstances should cable be 

pulled while the pump is being transported or installed. 

Attach a chain or rope to the grip and install the pump.

 

2. 

This pump must not be installed on its side or operated a 

dry condition. Ensure that it is installed upright on a 

 

secure base.

 

3. 

Install the pump at a location in the tank where there is 

the least turbulence.

 

4. 

If there is a flow of liquid inside the tank, support the  

piping where appropriate. 

5. 

Install piping so that air will not be entrapped. If piping 

must be installed in such a way that air pockets are  un- 

avoidable, install an air release valve wherever such air 

pockets are most likely to develop.

 

6. 

Do not permit end of discharge piping to be submerged, 

as backflow will result when the pump is shut down.

 

7. ! WARNING: 

Non-automatic pumps do not have an 

automatic operating system. Do not operate the pump for 

a long time with the water level near the lowest water 

level(H1) as shown in Fig.1, as the automatic cut-off 

switch incorporated inside the motor will be activated. 

8. 

To avoid dry operation, install an automatic operating

 

 system so that this will not happen, as shown in Fig.2 

and maintain a safe operating water level.

 

 

 

 

Electrical wiring 

1. 

Wiring 

A. 

Wire as indicated for the appropriate start system as 

shown in 

Fig-3. 

B. Loose connections will stop the pump. Make sure all 

electrical connections secure. 

2. 

Cable 

C. 

 

! WARNING: 

Never let the end of the cable con- 

tact water. 

D. If the cable is extended, do not immerse the splice 

in water. 

E. Fasten the cable to the discharge piping with tape or 

vinyl strips. 

F. Install the cable so that it will not overheat. Over- 

heating caused by coiling the cable and exposing it 

to direct sunlight. 

3. 

Grounding 

As shown in 

Fig-4 

ground the green wire (label E). 

Under no circumstances should the green wire be 

connected to the power supply. 

4. 

! WARNING: 

Use short circuit breakers to prevent 

danger of electrical shock. 

 

 

 

 

 

 

 

 

 

 

 

 

 

H1

Lowest water level (Motor flange) 

H2

Operating water level 

This must be above the top of the motor 

 

 

 

 

Operating Water Level 

 

 

 

 

Stop Water Level 

 

Fig-2 

Fig-3 

Fig-4 

 

on 

 

 

 

 

 

 

off 

Fig-1 

H2

 

H1

 

Содержание SEW Series

Страница 1: ...EI 700 006 REV 1 Installation Operation and Maintenance Manual Stancor SEW Series Pumps _______________________________________________________________________...

Страница 2: ...h the exception of shortening the cord to fit into a control panel Any splice between the pump and the control panel must be made within a junction box and mounted outside of the basin and comply with...

Страница 3: ...o during rainstorms water may be present in the surrounding area of the pump Caution must be used to prevent bodily injury when working near the pump Electrical power should be disconnected prior to t...

Страница 4: ...uring shipment Are any bolts or nuts loose Have all necessary accessories been supplied For a list of standard accessories see Construction We recommend that you keep a spare pump on hand in case of e...

Страница 5: ...op 6 Do not permit end of discharge piping to besubmerged as backflow will result when the pump is shut down 7 WARNING Non automatic pumps do not have an automatic operating system Do not operate the...

Страница 6: ...may be blocking the suction inlet 2 Regular inspections Monthly inspections Measure the insulation resistance The value should be more than 1M ohm If resistance starts to fall rapidly even with an ini...

Страница 7: ...7 Construction SEW DN 1 5 2HP...

Страница 8: ...200 11 Impeller FC 200 NO Name Mtrl NO Name Mtrl 1 Cable H07RN F SJTOW STOW 20 5 Washer SUS 304 13 Protector 3 Phase 20 7 Washer SUS 304 14 Capacitor 1 Phase 21 1 Spring Washer SUS 304 19 Screw SUS 30...

Страница 9: ...9 Construction SEW DN 3HP...

Страница 10: ...200 11 Impeller FC 200 NO Name Mtrl NO Name Mtrl 1 Cable H07RN F SJTOW STOW 20 5 Washer SUS 304 13 Protector 3 Phase 20 7 Washer SUS 304 14 Capacitor 1 Phase 21 1 Spring Washer SUS 304 19 Screw SUS 3...

Страница 11: ...filler plug and drain lubricating oil 4 Remove intermediate casing bolts and oil chamber Remember that any lubricating oil remaining in the mechanical seal chamber will flow out 5 Carefully remove mec...

Страница 12: ...ation 3 Correct rotation Does not pump Inadequate vol ume 1 Reverse rotation 1 Correct rotation see Operation 2 Significant drop in voltage 2 Contact electric power company 3 Operating a 60Hz pump wit...

Страница 13: ...Industrial Flow Solutions Operating LLC 104 John W Murphy Drive New Haven CT 06513 USA 860 399 5937 www flowsolutions com Stancor is a trademark of Industrial Flow Solutions Operating LLC All rights...

Отзывы: