Operating Instructions ProVicom
Assembly and disassembly
5 Assembly
and
disassembly
5.1 General information
Assembly and disassembly are subject to general technical rules. Additional, specific safety
regulations apply to electronic and pneumatic installations. In Germany, for example, these
include the BGI 547 (Information on and principles of workplace safety and health issued by the
Government Safety Association).
5.2 MT-65, MT-125
When installing the device, particular care shall be taken that:
•
the device has been properly installed according to instructions,
•
the device is undamaged,
•
all screws are tightened fast,
•
the device’s external bonding terminal is properly connected to the exponential bonding
system at its place of use.
5.3 Cut-out MT-xxx
Make a cut-out with the following dimensions:
Device Width
Height
Installation
depth
Material thickness
MT-65
275.0 ± 0.5 mm
131.0 ± 0.5 mm
max. 80 mm
up to 10 mm
MT-125
300.0 ± 0.5 mm
180.0 ± 0.5 mm
max. 80 mm
up to 10 mm
©
R. Stahl HMI Systems GmbH / OperatingInstruction_Provicom_Falcon_en_1_7.doc / 21.07.2008
Page 9 of 15