Temperature transmitter Ex i
Series 9182
Technical Data
Version
9182/10-51-12 and 9182/10-51-14, SIL 2
Output
Output signal
0/4 to 20 mA (configurable)
Functional range
0 to 21 mA
Connectable load
resistance R
L
1 channel
0 to 750
O
2 channels
0 to 600
O
Resolution
(
1
m
A
Settling time
(10 to 90 %)
(
35 ms
Delay input -
output
(
500 ms
Version
0/4 to 20 mA, passive / sink
9182/.0-59-1.
Passive output
Output signal
Current sink 0/4 to 20 mA (configurable)
Supply voltage
max. 31.2 V DC
Internal voltage
drop
(
3.0 V
Minimum load
resistance R
L
0 Ω at 3 to 20 V
200 Ω at 24 V
500 Ω at 30 V
Version
9182/.0-50-12 with limit contact, 9182/10-51-12 and
9182/10-51-14, SIL 2
Limiting values
Message
2 NO / NC
(configurable using ISpac Wizard)
Switching voltage
(
±30 V
Switching current
(resistive load)
(
100 mA
Switch on
resistance
(
2.5
O
(typical < 1
O
)
Reclosing lockout Reset using the DIP switch or "Power-Off" (configurable)