Assembling and Dismantling

6

212485 / 7579615300

2011-09-13·BA00·III·en·00

SolConeX Plug
G579/12

10 Assembling and Dismantling

Operating position

When unplugged, the plug should be suspended, with the contact pins pointing 

downward.

11 Installation

Electrical connection

The conductor must be carefully connected.

The conductor insulation must reach to the clamping points.

Do not damage the conductor (nicking) when removing the insulation.

Select suitable cables to be used and appropriate way of leading them to ensure that 
the maximum permitted conductor temperature and the maximum permitted surface 
temperature is not exceeded.

Protective conductor connection

A protective conductor is always required.

Connection

Loosen screws (A) and extract the plug insert manually from the enclosure.

Loosen clamp (C) and pressure screw (B).

Remove the dust protection plate, and take out the pressure ring and seal.

Push the cable (cable diameter max. 35 mm) through the pressure screw, 

pressure ring, seal and enclosure.

If necessary, increase the internal diameter of the seal by trimming it to match the 

cable diameter.

To protect the contact pins against pollution, a suitable protective cap should 
be used (For R. STAHL order no. see "Spare parts and accessories").

09192T00

A =

Screw

B =

Pressure screw

C = Clamp

D = Strain relief

E =

Guiding groove

Содержание G579/12

Страница 1: ...Operating Instructions SolConeX Plug G579 12 ...

Страница 2: ...Service 7 13 Maintenance Overhaul and Repair 8 14 Cleaning 8 15 Accessories and Spare Parts 8 16 Disposal 8 17 EC Declaration Of Conformity 9 2 General Information 2 1 Manufacturer R STAHL Schaltgeräte GmbH Am Bahnhof 30 74638 Waldenburg Germany Tel 49 7942 943 0 Fax 49 7942 943 4333 Internet www stahl ex com 2 2 Operating Instructions Information ID No 212485 7579615300 Publication Code 2011 09 1...

Страница 3: ...y regulations National and local accident prevention regulations National and local assembly and installation regulations Generally recognized technical regulations Safety instructions in these operating instructions Characteristic values and rated operating conditions on the rating and data plates Additional instruction plates fixed directly to the device 5 Conformity to Standards The relevant st...

Страница 4: ...al current 63 A 100 Hz 50 A Rated insulation voltage max 750 V Connection cross section max 16 mm2 Cable entries 24 36 mm cable diameter Tightening torque max 2 Nm Ambient temperature 20 40 C 45 55 C on request Enclosure material Polyamide Degree of protection IP66 acc to IEC EN 60529 Dimensional Drawings All Dimensions in mm Subject to Alterations 04511E00 mm A 260 B 84 C 69 5 D 112 ...

Страница 5: ...ode 09191E00 09196E00 3 P PE 3P N PE No of poles Frequency Rated operational voltage Colour code Earth contact position 3 P PE 50 and 60 Hz 100 130 V yellow 4 h 200 250 V blue 9 h 380 415 V red 6 h 60 Hz 440 460 V 1 red 11 h 50 and 60 Hz 480 500 V black 7 h 600 690 V black 5 h after isolating transformer 4 12 h 50 Hz 60 Hz 380 V 2 440 V 2 red 3 h 100 300 Hz 50 V green 10 h 3 300 500 Hz 50 V green ...

Страница 6: ...emperature and the maximum permitted surface temperature is not exceeded Protective conductor connection A protective conductor is always required Connection Loosen screws A and extract the plug insert manually from the enclosure Loosen clamp C and pressure screw B Remove the dust protection plate and take out the pressure ring and seal Push the cable cable diameter max 35 mm through the pressure ...

Страница 7: ...re putting into service Make sure that the components are not damaged Make sure that the device has been installed correctly Remove any foreign objects from the device Check if cable glands and stopping plugs are tight Check if screws and nuts are fastened tightly Inspect the cable glands for signs of damage Check the tightening torques Make sure that the bayonet lock is tightened correctly 09290T...

Страница 8: ...s lubrication after previous cleaning with the lubricating oil KLÜBERALFA KRA 3 730 is recommended 14 Cleaning The device may only be cleaned with a damp cloth 15 Accessories and Spare Parts 16 Disposal The national waste disposal regulations have to be observed WARNING Do not open when live The functioning of the plug must always be checked after any system short circuit WARNING It is not allowed...

Страница 9: ...212485 7579615300 2011 09 13 BA00 III en 00 EC Declaration Of Conformity 9 SolConeX Plug G579 12 17 EC Declaration Of Conformity ...

Страница 10: ......

Страница 11: ......

Страница 12: ...212485 7579615300 2011 09 13 BA00 III en 00 ...

Отзывы: