Explosion Proof Visual Signal -
5, 10 or 20 Joule
Series FL60
7.2.1 Installation conditions for electrical connection
7.2.2 Access to the PCB
DANGER
Risk of explosion!
Risk of injuries and material damage!
• Only cable glands with a corresponding certificate may be used.
They must be flameproof (Ex d), suitable for the type of cable used
and fulfil the requirements of IEC/EN 60079-14.
• Cable entry temperature may exceed 70 °C.
• To ensure the required ingress protection, installation of the cable gland
must be performed in accordance with the manufacturer's instructions.
• For unused enclosure holes use Ex d stopping plugs, for unused cable
glands Ex d plugs. Make sure that these components have an
appropriate approval and fulfil the requirements of IEC/EN 60079-14.
• All threaded cable entries to be fitted with an appropriately certified
component and the thread sealed with a suitable non-setting thread
sealant to maintain IP 66 rating.
DANGER
Danger due to energised parts!
Non-compliance results in severe or fatal injuries.
• Before opening and dismounting the device, disconnect it from the
power supply.
• Secure the device against unauthorized switching.
16439E00
• Remove cheese head screws x 4
• Carefully lift end cap
• Lift PCB to expose terminals for
connection (see wiring diagrams
for details)
• Remove protective flash tube cover