Emergency Luminaire with LED
Series EXLUX 6009/4
Through wiring
Assembly
Control gear
Emergency
light mode
In case of power failure the LEDs are supplied by the battery
Rated operating time at optimal ambient temperature of the battery:
Switchover voltage
From mains to battery operation
at U
N
= 230 V < 179 V
at U
N
= 110 V < 84 V
From battery to mains operation
at U
N
= 230 V > 190 V
at U
N
= 110 V > 94 V
Switching time
(
0.5 s
Battery set
Version
NiCd battery, gas-tight
Operating voltage
6 V
Capacity
7 Ah
Replacing the
battery set
When opening the battery enclosure, the connection between the battery
and the control gear is disconnected by means of a switch.
The battery set can be replaced after disconnecting the plug-in contacts.
Technical Data
Standard
luminaire
with
Luminaries are equipped with internal through wiring.
Connection of ingoing and outgoing leads on
opposite sites is possible.
Terminals: See Tech. data
Wiring cross section of the supply line connection:
2.5 mm
2
for max. 16 A
(Observe service temperature)
Optional
without
On the connection side, there are 2 bores M25 x 1.5
for cable entries for ingoing and outgoing wiring of the
connection line
(ingoing and outgoing leads on one side).
Standard luminaire
Standard:
2 x M8 insert nuts in the enclosure
Special:
Mounting grooves in the enclosure for use of fastening
and ceiling rails for variable luminaire mounting
(variable mounting distances for luminaires
L = 700 mm: 320 to 480 mm;
L = 1310 mm; 670 to 930 mm)
Battery
capacity
Rated operating
time
Emergency light output
Size 2
Size 4
7 Ah
1.5 h
65 %
35 %
3.0 h
35 %
20 %