Series EXLUX 6009/4

Wall bracket mounting

8.3

Installation

8.3.1 Opening and Closing of the Enclosure

15515E00

15517E00

Size

L4 mm [inch]

L mm [inch]

2

320 [12.60]

80 [3.15]

4

670 [26.38]

130 [5.12]

DANGER

Risk of electric shock due to improper opening!

Non-compliance results in severe or fatal injuries.

• Open luminaires without switch only in de-energized state  

(see information plate on the lock)!

Recommendation

Opening and closing of the luminaire by using a socket wrench from  

R. STAHL Schaltgeräte GmbH.

L

L

L4

10

x

15

°

Содержание EXLUX 6009/4 Series

Страница 1: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages www r stahl com EN Emergency Luminaire with LED Series EXLUX 6009 4...

Страница 2: ...d Use 6 3 4 Modifications and alterations 6 4 Function and device design 6 4 1 Function 6 4 2 Device design 7 5 Technical data 9 6 Engineering 13 6 1 Mains operation 13 6 2 Emergency light blocking 14...

Страница 3: ...eclaration of Conformity www r stahl com The device has IECEx approval For certificate please refer to the IECEx homepage http iecex iec ch Further national certificates can be downloaded via the foll...

Страница 4: ...Type and source of danger damage Consequences of danger Taking countermeasures to avoid the danger or damage Symbol Meaning Tips and recommendations on the use of the device Danger due to explosive a...

Страница 5: ...y the technical data We cannot be held liable for damage to the device caused by incorrect or unauthorised use or non compliance with these operating instructions For assembly and installation Observe...

Страница 6: ...re is approved for use in hazardous areas of Zones 1 21 2 and 22 Mode of operation A weekly functional test has been permanently integrated An annual rated operating time test can be deactivated and a...

Страница 7: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Emergency Luminaire with LED Series EXLUX 6009 4 4 2 Device design 20300E00 1 I S Module 5 Cable entry 2 Control gear 6 Connection te...

Страница 8: ...300190 2018 11 09 BA00 III en 00 EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Emergency Luminaire with LED Series EXLUX 6009 4 20301E00 9 LED indicator 11 LED PCB 10 Moun...

Страница 9: ...Certifications and certificates Certificates IECEx ATEX Technical Data Electrical data Rated operational voltage AC 110 to 230 V 10 50 to 60 Hz Rated operational current Power factor Rated insulation...

Страница 10: ...IK10 IEC 62262 Luminous characteristics Colour rendering Ra 80 Colour temperature 4 000 K 5 000 K or 6 500 K depending on the variant Luminous flux Values apply to Ta 25 C Luminous flux decrease at a...

Страница 11: ...n glass fibre reinforced Colour Grey colour similar to RAL 7035 Seal Silicone seal foamed into the translucent cover Translucent cover Polycarbonate Luminaire locking Central lock for M8 A F 13 box sp...

Страница 12: ...s disconnected by means of a switch The battery set can be replaced after disconnecting the plug in contacts Technical Data Standard luminaire with Luminaries are equipped with internal through wiring...

Страница 13: ...e light fitting is switched off 6 1 2 Continuous operation The light fitting is switched on Optional DALI connection DALI interface in accordance with IEC 62386 202 2009 08 and IEC 62386 207 2009 08 B...

Страница 14: ...ng 6 2 Emergency light blocking A remote switch for emergency light blocking can be connected to terminals 10 and 12 of the control gear 16399E00 18475E00 Remote switch is closed Remote switch is open...

Страница 15: ...The remote switch is directly connected to the control gear The following connection versions are possible Point to point connection Linear connection The following conductor specifications must be o...

Страница 16: ...of deep battery discharge due to exceeded storage Non compliance can result in material damage The battery should be charged within 26 weeks from date of production by means of operating the luminair...

Страница 17: ...drawings for assembly parts and accessories all dimensions in mm inches Subject to alterations 15778E00 15779E00 Mounting rail M25 x 1 5 183 5 7 22 125 L3 L2 L1 L3 L2 4 92 M25 x 1 5 Dimen sions Lumin...

Страница 18: ...ing bracket fitted in mounting rail Pipe clamp fitted in mounting rail 15780E00 03257E00 Wall mounting bracket fitted in mounting rail Bracket for wall mounting with pipe section 17755E00 Dimensions L...

Страница 19: ...avoided accidental friction particle currents DANGER Explosion hazard due to inadmissible heating Non compliance results in severe or fatal injuries Avoid external heat sources and or direct sunlight...

Страница 20: ...mounting sleeve 16325E00 16326E00 Mounting bracket Top rail Lateral mounting pockets for variable points of suspension When mounting the luminaire using top rails ensure that the mounting surface is...

Страница 21: ...ion Pole mounting using pipe clamps 16327E00 16328E00 Size L4 mm inch L mm inch 2 320 12 60 80 3 15 4 670 26 38 130 5 12 For pipe clamp mounting use the solution of R STAHL Schaltger te GmbH with inte...

Страница 22: ...Opening and Closing of the Enclosure 15515E00 15517E00 Size L4 mm inch L mm inch 2 320 12 60 80 3 15 4 670 26 38 130 5 12 DANGER Risk of electric shock due to improper opening Non compliance results i...

Страница 23: ...tral lock opening protection against dirt Observe the following during mounting and dismounting Version without switch Disconnect the luminaire from the power supply secure it against being switched o...

Страница 24: ...onnecting to the main supply Clamping must be carried out precisely Do not clamp any part of the conductor insulation Do not interchange the conductors Observe the technical regulations when connectin...

Страница 25: ...lamping range 1 x 1 5 to 6 mm2 solid finely stranded 2 free clamping units per pole available Stripping length 10 to 12 mm Standard 20294E00 with DALI connection 20302E00 Through wiring with 2 5 mm2 c...

Страница 26: ...tightened using the following values Luminaires with approved cable entries and stopping plugs not supplied by R STAHL Schaltger te GmbH 18475E00 Clamping range 1 5 mm2 solid finely and extra finely s...

Страница 27: ...en inserted correctly Check if all screws and nuts have been tightened firmly Check if all drilled holes are closed Check whether all the cable entries and stopping plugs have been tightened firmly Ch...

Страница 28: ...rgency light operation The luminaire is switched on regardless of the operation mode of the selected rated operating time Rated operating time Stand by operation The luminaire is switched off regardle...

Страница 29: ...s shown on the LED indicator During a test the luminaire is switched on Function test starts within 24 hours after commissioning is carried out every 7 days takes 1 minute checks the function of the L...

Страница 30: ...Function test green LED 2 to 4 Function test red LED 4 to 10 Status rated operating time test Green LED flashes rated operating time test active Green LED off rated operating time test not active Gree...

Страница 31: ...ber of the device Purchase information Error description Intended use in particular input output wiring Cause of error Troubleshooting The LEDs are defective Replace the mounting plate including LEDs...

Страница 32: ...signs of ageing or damage completely replace enclosure components with damaged foamed seal Whether the device is clean inside and out Whether the permissible temperatures in accordance with EN 60079 a...

Страница 33: ...Lift the translucent cover to detach it from the hinge Insert new translucent cover into the hinge All hinges must engage correctly Close the luminaire Observe safety notes DANGER Explosion hazard du...

Страница 34: ...N EN Emergency Luminaire with LED Series EXLUX 6009 4 Loosen the screws 1 cross head H2 in the battery cover 2 Open the battery case The switch 6 disconnects the battery circuit Secure the battery cov...

Страница 35: ...et jammed Tighten the screws 1 cross head H2 firmly 2 Nm Resetting the error indication blinking red after replacing the battery 16406E00 The error indication blinking red remains active after success...

Страница 36: ...tion will be sent R STAHL s customer service will contact you You will receive an RMA slip after speaking with customer service Send the device along with the RMA slip in the packaging to R STAHL Scha...

Страница 37: ...due to chemical reactions Human health and the environment are at risk Batteries collect them separately dispose of them in controlled fashion do not dispose of them in the domestic waste return them...

Страница 38: ...arking marquage r v II2 G Ex db eb ib mb op is IIC T4 Gb r r W II2 D Ex tb op is INC T 100 C Db V S 0158 EU Baumusterpr fbescheinigung EU Type Examination Certificate Attestation d examen UE de type I...