Linear Luminaire for Fluorescent Lamps
Series EXLUX 6001
7
Mounting and installation
7.1
Dimensions / fastening dimensions
DANGER
Explosion hazard due to incorrect installation of the device!
Non-compliance results in severe or fatal injuries.
• Carry out installation strictly according to the instructions and national
safety and accident prevention regulations to maintain the explosion
protection.
• Select and install the electrical device so that explosion protection is not
affected due to external influences, i.e. pressure conditions, chemical,
mechanical, thermal and electric impact such as vibration, humidity and
corrosion (see IEC/EN 60079-14).
• The device must only be installed by trained qualified personnel who is
familiar with the relevant standards.
NOTICE
Malfunction or device damage caused by condensation.
Non-compliance can result in material damage!
• operate the luminaire continuously or periodically over extended periods of time.
• avoid thermal bridges.
Dimensional drawings (all dimensions in mm [inches]) – Subject to modification
15440E00
EXLUX 6001 Standard luminaire
Dimen-
sions
Light fitting
Size 2
Size 4
Size 6
L1
700 [27.56]
1310 [51.57]
1610 [63.39]
L2
1)
400 [15.75]
800 [31.50]
800 [31.50]
L3
2)
320 to 480 [12.60 to 18.90] 670 to 930 [26.38 to 36.61] 670 to 930 [26.38 to 36.61]
b
184 [7.24]
184 [7.24]
184 [7.24]
h1
125 [4.92]
125 [4.92]
125 [4.92]
1)
fixed mounting distance
2)
variable mounting distance