Mounting and Installation
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Termination board and
connecting cable for Zone 2
Series 9491
Connection between I/O modules and termination board
The termination board 9491/T1-08-0. in combination with two connecting cables
9491/Z1-VB-.. enables the redundant interconnection of two type 9469/35 I/O modules.
22373E00
Connect a 9491/Z1-VB-.. connecting cable with pre-installed, 24-pole,
pluggable terminal on the cable end on the X1 terminals of the primary and redundant
I/O modules and use the safety screws to secure it from loosening
(tightening torque 0.5 to 0.6 Nm).
Connect the cable end with the Sub-D plug from the primary I/O module terminal X1 to the
Sub-D socket X1P on the termination board and use the safety screws to secure it against
loosening (tightening torque 0.5 to 0.6 Nm).
Connect the cable end with the Sub-D plug from the redundant I/O module terminal X1 to
the Sub-D socket X1R on the termination board and use the safety screws to secure it
against loosening (tightening torque 0.5 to 0.6 Nm).
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
primary
I/O module
X1
X1P
X1R
X1B
X1A
X1
redundant
I/O module