IS1+ power module for Zone 2 / Division 2
Series 9445/35
6.2.2 Upgrade of the IS1 9440/15 PROFIBUS CPM Series to
IS1+ 9442/35 CPU + 9445/35 Power 9496/35 Base
Switch off the power supply to the IS1 Remote I/O Station (9440/15 CPM).
Unscrew the knurled screws on the auxiliary power plug of 9440/15 CPM on the reverse
side and disconnect the plug.
Disconnect the connection lines for communication.
Pull the blue or red notch lever of the 9440/15 CPM upwards to unlock the module.
Pull the 9440/15 CPM up to remove it from the 9494 BusRail.
Replace the auxiliary power plug plus connected cable with the IS1+ auxiliary power set.
Mount the 9496/35 base (see the 9496/35 operating instructions).
Mount the IS1+ communication assembly in accordance with Chapter 6.1.2 and
the 9442/35 operating instructions.
6.2.3 Upgrade of the IS1 9441/15 Ethernet CPU Series to
IS1+ 9442/35 CPU + 9445/35 Power 9496/35 Base
Remove the IS1 Ethernet CPU and power module
(see the 9441/15 operating instructions).
Switch off the power supply to the IS1 9492/15 Ethernet base.
Dismount the 9492/15 base (see the 9441/15 operating instructions).
Mount the 9496/35 base (see the 9496/35 operating instructions).
Mount the IS1+ communication assembly in accordance with Chapter 6.1.2 and
the 9442/35 operating instructions.
6.3
Installation
Unlike the 9492/15 IS1 Ethernet base, the 9496/35 base of the IS1+ CPU is connected
to the slot (slot 1) of the BusRail. This moves all I/O modules by one slot (slot n+1).
Then the system has to be reconfigured! If there is space available,
a 9494/S1-B2 BusRail can also be connected at the beginning.
Operation under difficult conditions, in particular on ships, requires additional
measures to be taken for correct installation, depending on the operating location.
Further information and instructions on this can be obtained from your regional sales
contact upon request.