Parameterization and commissioning
Before commissioning, ensure the following:
• Installation of the device according to regulations.
• Correct connection of the cables.
• No damage at the device and connection cables.
• Tight seat of the screws at the terminals. Correct tightening torque: 0.5 ... 0.6 Nm.
9.1
Replacement of the device
• If replacing by a device with identical design, readjust the DIP switch, if necessary.
9.2
Overview of functions
*) Bit retiming only from 93.75 kBit
9.3
DIP switch settings 9185/11-35-10
See device labelling.
9.4
DIP switch settings 9185/11-45-10
See device labelling.
9.5
DIP switch settings 9185/12-45-10
See device labelling.
Changing the switch settings is also permitted during operation in Zone 2
and with connected intrinsically safe input signals.
Incorrect parameterization or an incorrect update can result in the device
not working properly.
• Please carry out parameterization carefully and exactly as per the
instructions.
Type
Field side (X3) RS2 switch
Auto baud rate
detection
Bit retiming *)
Full duplex
9185/11-35-10 RS-485 IS
any
Yes
(PROFIBUS)
Yes
No
9185/11-45-10 RS-485 Ex i
OFF
Yes
(PROFIBUS)
Yes
No
RS-422 Ex i
ON
No
No
Yes
9185/12-45-10 RS-485
OFF
Yes
(PROFIBUS)
Yes
No
RS-422
ON
No
No
Yes