Floodlight
Series 6521/5
7.3
Installation
7.3.1 Opening and Closing of the Enclosure
7.3.2 Electrical connections
Electrical connection
Observe the maximum clamping possibility of the connection terminals
(see chapter "Technical data").
Observe the following when connecting to the electrical connection:
• Clamping must be carried out precisely.
• Do not clamp any part of the conductor insulation.
• Do not mix up the conductors.
• Observe the technical regulations when connecting the conductor.
• Clamp the conductor firmly.
Connection terminals
DANGER
Risk of electric shock due to improper opening!
Non-compliance results in severe or fatal injuries.
• Open luminaires without switch only in de-energized state
(see information plate on the lock)!
17216E00
Opening:
• Loosen the M6 (allen key 5) cover
screws.
• Open the cover.
Closing:
• Close the cover.
• Firmly tighten the cover screws
(tightening torque 2.5 Nm).
Clamping range:
0.5 to 6 mm
2
Stripping length:
10 to 11 mm
Standard:
21968E00
N
L1
L1
N
3-pole
L1
= phase
N
= neutral conductor
PE
= protective
conductor