Pendant Light Fitting LED
Series 6470/5
7.3.3 Cable entries
Luminaires with cable entries and stopping plugs which are not supplied by
R. STAHL Schaltgeräte GmbH
Please observe the following:
• the required dust resistance!
• the required type of protection!
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable entries and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
• Insert the metal cable entries and/or stopping plugs into the PE!
DANGER
Explosion hazard due to impermissible cable entries and stopping plugs!
Non-compliance results in severe or fatal injuries.
• Only use separately certified cable glands and stopping plugs which
have been tested and certified according to Directive 2014/34/EU
(ATEX) or IECEx (CoC) and which comply with the standard version
stated in the certificate of the luminaire.
DANGER
Explosion hazard if breathers are used!
Non-compliance results in severe or fatal injuries.
• Do not use breathers.
Cable glands and stopping plugs must be approved for the following types of
protection:
a) restricted breathing (nR) and dust (IIIC)
b) increased safety (e)