Universal spotlight LED
Series 6050/6
7.3
Installation
7.3.1 Electrical connections
DANGER
Explosion hazard due to opening the enclosure cover!
Non-compliance results in severe or fatal injuries.
• It is prohibited to open the enclosure cover of the luminaire.
DANGER
Explosion hazard due to faulty installation!
Non-compliance results in severe or fatal injuries.
• Only use conductor provided by the manufacturer for explosive areas.
• Make sure that the IP protection is preserved after installation.
• Comply with the relevant conductor cross-section:
• 0.2 to 6 mm
2
(solid)
• 0.2 to 4 mm
2
(finely-stranded)
• 0.2 to 6 mm
2
(finely stranded with core end sleeve)
20010E00
20148E00
• Loosen the M6 Torx screws (1) and
remove the cover.
• Loosen cable entry (2)
(unscrew approx. 3 rotations).
• Insert cable into the terminal box from the
outside through the cable entry.
• Strip approximately 10 mm of the cable
using an appropriate tool.
• Unlock the screwless terminals (3) using a
screwdriver and insert the cable. Make sure
that the conductor insulation is not inserted
into the terminal.
• Lock cable entry firmly by tightening
completely.
• Re-attach the cover and close it using the
respective screws. The light fitting is now
operational.
2
PE N
1
2
3
3