Mounting and Installation
13
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Socket for CPU and power modules
for Zone 1
Series 9496/32
6.1.5 Upgrading to the IS1+ CPU and Power Module
When upgrading from IS1 to IS1+, replace components according to the following table.
6.2
Installation
This device does not require an (electrical) installation.
Installed
New
IS1 Ethernet
Remote I/O
IS1 RS485
Remote I/O
IS1+ Ethernet/RS485
Remote I/O
CPU
9441/12
9440/22
9442/32
Power module 9444/12
9445/32
Socket
9492/12-11
9490/1x-12
9496/32
The socket with four slots is wider than a slot on the BusRail, which means that it occupies
the first slot of the BusRail and protrudes left over the BusRail by 56 mm.
When upgrading from IS1 Ethernet Remote I/O (9441/12 with 9444/12 and 9492/12-11)
to IS1+ Ethernet/RS485 Remote I/O (9442/32 with 9445/32 and 9496/32), please note
the following:
Compared with the previous model 9492/12-11, on which the BusRail is attached
laterally, the new socket 9496/32 occupies its own slot on the BusRail. This means that
all modules attached to the BusRail must be reconnected to the right by a slot (n+1),
see figure. The configuration must be adapted!
20591E00
20592E00
IS1 Ethernet Remote I/O
(9441/12 with 9444/12 and 9492/12-11)
IS1+ Remote I/O
(9442/32 with 9445/32 and 9496/32)