Mounting and Installation
12
290163 / 949660310110
2021-08-05·BA00·III·en·00
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Socket for CPU and power modules
for Zone 1
Series 9496/32
6.1.3 Dismounting the BusRail (DIN Mounting Rail)
▶
Disconnect the power module(s) from the supply.
▶
Remove the CPU and power module(s) (see the respective operating instructions).
▶
Use a suitable tool to loosen all safety screws from the socket.
▶
Remove the socket vertically from the BusRail.
6.1.4 Replacing the Socket
▶
Disconnect the power module(s) from the supply.
▶
Remove the CPU and power module(s) from the socket
(see the operating instructions for the CPU or power module).
▶
Dismount the installed socket and mount the new socket as described in chapters 6.1.3
and 6.1.4.
▶
Readjust the protocol and PROFIBUS DP/RS485 +SB address (if necessary) on the new
socket, see chapter 7.2.
▶
Clean the surface between the CPU, power module and socket, and keep it clean.
DANGER! Explosion hazard due to work on a live socket!
Non-compliance results in fatal or severe injuries.
▶
Disconnect all connected modules and devices from the supply before connecting
the socket to or disconnecting it from the BusRail.
18452E00
20588E00
DANGER! Explosion hazard due to work on a live socket!
Non-compliance results in fatal or severe injuries.
▶
Disconnect all connected modules and devices from the supply before connecting
the socket to or disconnecting it from the BusRail.