Technical Data
4
145955 / 8510601300
2011-11-21·BA00·III·en·02
Control Unit
8510/1
6
Technical Data
Explosion protection
Global (IECEx)
IECEx BVS 07.0029U
Ex d e [ia] IIC, Ex d e I
Europe (ATEX)
DMT 00 ATEX E 073 U
E
II 2G Ex d e [ia] IIC resp.
E
I M2 Ex d e I
Material
Enclosure material
Epoxy resin
Terminal cover
Polyamide; IP20, finger-contact safety according to IEC/EN 60529
Ambient temperature
- 20 °C ... + 40 °C
Rated operational voltage U
e
max. 690 V
Rated operational current
Main contacts
up to 10 A (2.5 mm
2
)
up to 45 A (10 mm
2
)
Auxiliary contacts
up to 6 A
Conductor cross-section
Main contacts
Auxiliary contacts
0.75 ... 1.5 mm
2
flexible
0.75 ... 2.5 mm
2
solid
Tightening torque
Main contacts
1.8 ... 2.0 Nm (10 mm
2
)
1.0 ... 1.2 Nm (2.5 mm
2
)
Auxiliary contacts
1.0 ... 1.2 Nm (2.5 mm
2
)
WARNING
Please observe the technical data on the rating plate.
Please consult the manufacturer if operating conditions are non-standard.
1 or 2 cables can be connected. If solid, both conductors must have the same
cross-section.
8510/11.
0.75 ... 1.5 mm
2
, finely-stranded
0.75 ... 2.5 mm
2
, solid
8510/122; 8510/131
8510/132; 8510/141
1.5 ... 6 mm
2
, finely-stranded
1.5 ... 10 mm
2
, solid
Содержание 145789
Страница 1: ...Betriebsanleitung Operating Instructions Steuerger t Control Unit 8510 1...
Страница 2: ......
Страница 3: ...Betriebsanleitung Steuerger t 8510 1...
Страница 10: ...145955 8510601300 2011 11 21 BA00 III de 02...
Страница 11: ...Operating Instructions Control Unit 8510 1...
Страница 18: ...145955 8510601300 2011 11 21 BA00 III en 02...
Страница 19: ......
Страница 20: ...145955 8510601300 2011 11 21 BA00 III de en 02...