Page | 7
Attaching the Cabinet to the UPS
The Maintenance Bypass Switch cabinet was constructed so that it can be mounted to the
side of the UPS cabinet if desired. To attach the Maintenance Bypass Switch Cabinet to
the UPS Cabinet:
1. Remove right side panel of UPS and save hardware.
2. Butt left side of MBS cabinet up against the right side of the UPS.
3. Bolt the cabinets together at (6) locations with the supplied 5/16 hardware through
the slots noted as "A" in
Figure 3
.
4. Mount right side panel of UPS on the right side of the MBS cabinet using the
hardware from the UPS.
Figure 3 - Cabinet to Cabinet Mounting Hole Locations
LEFT SIDE VIEW
A
A
A
A
A
A