Note:
The Cycle time and On time Limits are tied together; you are not allowed to
make cycle time shorter than the On time Limit and you can not increase the On Time
Limit longer than the Cycle time. Depending on which one that you are increasing or
decreasing the other may increase or decrease with it.
Examples: 1. If “Cycle time” is 600 seconds and you tried to increase “On
time Limit” to 720 seconds the “Cycle time” would automatically increase to
720 seconds.
2. If “On time Limit” was set for 120 seconds and you decreased
the “Cycle time” to 60 seconds; the “On time Limit” would automatically
change to 60 seconds.
3.9 ON TIME LIMIT
Pressing either the pH or ORP Menu buttons three times lets you set the maximum time
that you want the controller to be “on” during the cycle time. This allows you have a
minimum off time before the beginning of the next cycle. For example, if you have a
Cycle Time of 12 seconds and an On Time Limit of 5 seconds the minimum off time would
be 12 – 5 = 7 seconds. Pressing the + button will increase the time value and pressing
the - will decrease the time value that you want to set. (Pressing the + or – buttons
momentarily will increase or decrease the time values one (1) second at a time. Holding
down the + or – button it will increase or decrease the time by ten (10) second
increments.)
Note: The time is set in seconds. The maximum value for cycle time that you can input is
900 seconds. (15 minutes).
pH On time Limit Display
pH
060
ORP
pH pH Flow ORP ORP
FEED ALARM
ALARM FEED