10. Unscrew the bolts that attach the manifold adapter to

the tube sheet and remove the manifold adapter and
the inlet/outlet manifold as a unit.

11. Carefully disconnect all three metering tubes from the

Combustion Air Blower Assembly (1 to the Combination
Gas Control Valve, 2 to the Air Flow Switch).

12. Remove the bolt from the Gas Piping Clamp. 
13. Unplug all wires to the Control Box. Unscrew three

nuts and remove the Control Box, the Heat Shield, and
the Membrane Pad and Cover as a unit (See Figure 2,
Key  No. 4).

14. Unscrew the four nuts holding the Blower Adapter

Plate to the top of the Combustion Chamber and
remove the Combustion Air Blower, the Igniter, the
Combination Gas Valve and associated piping and the
Blower Adapter Plate as a unit (See Figure 2, Key No.
5). Remove the Flameholder and Flameholder Cone (if
used).

NOTICE: 

BE CAREFUL not to break or crack the igniter

– it is fragile!

15. Unscrew the nuts holding the Combustion Chamber

top to the Combustion Chamber body.

16. Unscrew 4 hold-down nuts from the hangers support-

ing the Combustion Chamber.

17. Wrap a shop rag around each hanger, one at a time (be

careful; it’s sharp) and hammer down on the Lower
Enclosure while lifting the hanger by the shop rag. This
will lift the hanger up off of the hold-down bolt. 

18. Lift the Combustion Chamber out of the Lower

Enclosure.

Heavy parts; can cause personal injury.

When lifting, use all proper precautions for the weights
involved.

19. Cut the RTV all the way around the top of the

Combustion Chamber with a screwdriver.

20. With a mallet and screwdriver, go around the

Combustion Chamber cover tapping 

up

until the RTV

separates and releases the Combustion Chamber cover.
Be careful not to damage the Combustion Chamber.

21. Remove the Combustion Chamber cover. 

California’s Proposition 65 lists

Refractory Ceramic Fibers heated to 1800° F or higher
as a possible human carcinogen. 

See the warning box

on Page 6 for further information. Call 1-800-752-0183
for a Material Data Safety Sheet (MSDS).

22. Remove the top insulation, the Heat Exchanger Coil,

the Condensate Evaporator, the Bottom Insulation, and
the metal spacer from the Combustion Chamber. Do
not remove the RTV that seals the manifold mounting
plate to the combustion chamber.

23. Clean up the Combustion Chamber, the Combustion

Chamber cover, and the Spacer. Be sure to completely
remove all RTV from the Combustion Chamber and
Combustion Chamber top.

24. Reinstall the clean spacer in the Combustion Chamber.

Install one 1/2” white Insulation Blanket on top of the
spacer and one piece of 1” “M” insulation on top of the
Blanket. Make sure that the insulation is centered in the
Combustion Chamber.

NOTICE: 

Model SR/SRC200 heaters built before 1/1/98

require two 1/2” Insulation Blankets.

2

5

3

1

4

Figure 2: Removal of major sub-assemblies

1/2" Top 
Blanket

1" Top
Insulation

1/2" Bottom
 Blanket

1" Bottom
"M" Insulation

Flameholder
Insulation
Cap (Tape
to bottom of 
Flameholder)

Spacer

Condensate
Evaporator

Flameholder

3122 1197

Figure 3: Correct order for installation of insulation.

Содержание SR

Страница 1: ...et Delavan WI 53115 North America 800 752 0183 FAX 800 582 2217 International 262 728 5551 FAX 262 728 4461 TELEX ITT 4970245 www sta ritepool com Union City TN Delavan WI Mississauga Ont Murrieta CA 2003 Sta Rite Industries Inc Printed in U S A S430 Rev 2 14 03 ...

Страница 2: ...lectrical power to the heater Close the external Manual Gas Valve 2 If the heater is below the water level of the pool close the isolation valves to avoid draining the pool 3 Remove the drain plug under the manifold and drain the heater 4 While the heater is draining remove the upper left and upper right jacket halves 5 Remove the switch covers on both sides of the mani fold and unplug the wires f...

Страница 3: ...the weights involved 19 Cut the RTV all the way around the top of the Combustion Chamber with a screwdriver 20 With a mallet and screwdriver go around the Combustion Chamber cover tapping up until the RTV separates and releases the Combustion Chamber cover Be careful not to damage the Combustion Chamber 21 Remove the Combustion Chamber cover California s Proposition 65 lists Refractory Ceramic Fib...

Страница 4: ...of bolts into it and pull it back in place Brush off all dust and debris with a brush and wipe it down with a cloth Apply silicone grease supplied to O Rings Clean the tube sheet and O ring sealing surface with a nylon brush then brighten the tube sheet surface with 320 grit emery cloth 1 2 3 Figure 4 Clean the Tube Sheet and O Ring sealing sur faces thoroughly as described above Figure 6 Install ...

Страница 5: ...ociated piping and the Blower Adapter Plate as a unit use new gaskets Be sure to reinstall the Insulation Cap on the bottom of the Flameholder Tighten Adapter Plate nuts to 70 80 in lbs torque See Figure 9 1 2 3 6 7 10 5 4 9 8 75 115 in lbs 8 4 12 9 N m Torque Pattern All Models 1 Make sure that all bolts are engaged and hand tight 2 Torque the bolts in sequence as shown Some noise popping etc is ...

Страница 6: ...om of Junction box in Flexible Conduit Wiring Harness to Control Box Black to Black White to White Green Ground to Green Ground Bonding Wire View From Above Interior Figure 10 Junction Box Wiring Connections For detailed installation operation maintenace and safety information about the Sta Rite pool heater call customer service at 1 800 752 0183 and request a Sta Rite Pool Spa Heater Training and...

Страница 7: ...1 L2 BM FL F1 L2 S2 TH IND VAL GND GND GND GND BLOWER 120VAC 120VAC HOT 120VAC IGNITER MOT TRANS TRANS GROUND GND NEUTRAL NEU JUNCTION BOX F I R E M A N S S W I T C H Replace jumper with leads to Fireman s Switch field installed 24VAC SEC PRIM 120VAC Y W Y W Y R Y O Y BL BK GY GY BK BK W W BK W W W W G G Y Y Y Y BK BK Y W W W R R BL BL O O O O PR PR Y R Y BL Y O Y W Y Y Y Y Y Y Y Y Y BR BR 3661 02...

Страница 8: ...nsulation Cap 1 42001 0075 2 1 2 Blanket 1 42001 0071 3 1 Top Insulation 1 42001 0070 4 Condensate Evaporator 1 42001 0065 5 1 M Insulation 1 42001 0072 6 1 2 Blanket 1 42001 0073 1 2 3 4 6 5 3125 1197 Model SR SRC200 heaters built before 1 1 98 use 2 of Part No 42001 0073 ...

Отзывы: