To Convert 230 Volts to 115 Volts, Plug-in type
(see Figures 5 and 6).
1. Unplug the motor.
2. Loosen the two screws on the end of the motor.
Gently pull the canopy from the motor.
NOTICE
: Do not pull or jerk wires.
3. Connect the green (or bare copper) ground wire to
the green ground screw first. Use a solid copper
wire at least as large as the power supply wires.
4. Pull the plug straight out from the terminal board,
from 230 Volt socket.
5. Plug in again with arrow on plug pointing to 115
Volts.
6. Change is complete.
NOTICE:
Some models are equipped with three phase
motors. Three phase motors require magnetic starters
and can run in either direction, depending on how they
are connected to the power supply.
6
TABLE II - RECOMMENDED FUSING AND WIRING
Branch
Max.
Fuse
Wire Length
Motor
Motor
Volts/
Load
Rating
0’-100’
101-200’
201-300’
Type
H.P.
Phase
Amps
Amps
AWG Wire Size
ODP
1/2
115/230/1
12.4/ 6.2
20/15
12/14
10/14
8/14
ODP
1/2
230/460/3
3.1/1.55
15/15
14/14
14/14
14/14
ODP
3/4
115/230/1
14.8/7.4
20/15
12/14
8/14
6/14
ODP
3/4
230/460/3
3.6/1.8
15/15
14/14
14/14
14/14
ODP
1
115/230/1
19.2/9.6
25/15
10/14
8/14
6/12
ODP
1
230/460/3
4.7/2.35
15/15
14/14
14/14
14/14
ODP
1-1/2
115/230/1
24/12
30/15
10/14
6/12
6/12
ODP
1-1/2
230/1
12.0
15
14
14
12
ODP
1-1/2
230/460/3
6.8/3.4
15/15
14/14
14/14
14/14
ODP
2
115/230/1
26/13
35/20
8/12
6/12
4/10
ODP
2
230/1
10.4
15
14
14
14
ODP
2
230/460/3
6.0/3.0
15/15
14/14
14/14
14/14
ODP
3
208-230/1
15.0
20
12
12
10
ODP
3
200-230/460/3
11.5/5.8
15/15
14/14
14/14
12/14
TEFC
1
115/230/1
18/9
25/15
10/14
8/14
8/12
TEFC
1
208-230/460/3
4.8/2.4
15/15
14/14
14/14
14/14
TEFC
1-1/2
230/1
10.4
15
14
14
12
TEFC
1-1/2
208-230/460/3
6.0/3.0
15/15
14/14
14/14
14/14
TEFC
2
230/1
11.7
15
14
10
8
TEFC
2
208-230/460/3
7.0/3.5
15/15
14/14
14/14
14/14
TEFC
3
230/1
TEFC
3
208-230/460/3
7.0/3.5
15/15
14/14
14/14
14/14