![SSTOMM GT200-DP-MT Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/sstomm/gt200-dp-mt/gt200-dp-mt_user-manual_1355332009.webp)
User Manual
PROFIBUS DP Modbus TCP
/
Gateway
GT200-DP-MT
WWW.SSTCOMM.COM
9
Notes:
Restart GT200-DP-MT (power off and power on) after resetting the configuration to make the
configuration take effect!
3.3.2 PROFIBUS DP Address Setting Switch
The 2-code rotary switch in the left-side is used for setting the PROFIBUS DP address of the device.
In this example, the calculation formula of PROFIBUS DP address will be: 42 ((4x10) + (2x1)).
3.4 Connectors
3.4.1 PROFIBUS DP Connector
DB9 pin
Function
3
PROFI_B, Data positive
5
GND
8
PROFI_A, Data negative
PROFI-B
PROFI-A
GND
PROFI-B
PROFI-A