User Manual
PROFIBUS DP Modbus TCP
/
Gateway
GT200-DP-MT
WWW.SSTCOMM.COM
5
2 About the Gateway
2.1 Function
Connects Modbus TCP devices to PROFIBUS DP network, and establishes communication between them.
2.2 Features
With an Ethernet interface (Modbus TCP master / Modbus TCP slave) and a PROFIBUS DP slave interface
Ethernet 10/100M adaptive
IP address conflict detection
Support DHCP, BOOTP and static setting
Support standard Modbus TCP master and slave protocol
I/O data monitoring capabilities
Easy-to-use configuration software SST-EP-CFG
2.3 Technical Specification
[1]
Support PROFIBUS DP V0 protocol;
[2]
PROFIBUS DP slave, baud rate adaptive, maximum baud rate 12M;
[3]
PROFIBUS DP max input data bytes is 244 bytes and output data bytes is 244 bytes, input + output data
bytes is 488 bytes;
[4]
As a Modbus TCP master, it can support visiting Modbus TCP server of at most 36 different IPs or
different unit IDs;
[5]
As a Modbus TCP master, it can support the function code: 01H, 02H, 03H, 04H, 05H, 06H, 0FH and
10H;
[6]
As a Modbus TCP slave, it can support up to 36 TCP connections;
[7]
As a Modbus TCP slave, it can support the function code: 03H, 04H, 06H and 10H;
[8]
PROFIBUS DP interface: 1KV photoelectric isolation;
[9]
Power supply 24VDC (11V to 30V), 160mA (24VDC);
[10]
Operating temperature: -4 ° F to 140 ° F (-20
℃
~60
℃
), relative humidity 5% ~ 95% (no condensation);
[11]
External Dimensions (W*H*D): 1.57in*4.92in*4.33in (40mm* 125mm * 110mm);
[12]
Installation: 35mm rails;
[13]
Protection class: IP20;
[14]
Test standard: Complies with EMC test standards.