As is shown above, the data modules which GT200-DP-MT supports include: Word consistency, Byte
consistency and length consistency.
For the data modules that support Word and Byte consistency, you can use command “MOVE” to access the
data during STEP7 programing.
For the data modules that support length consistency, user can take compression way to send and receive data.
The compression way mainly uses “SFC 15” when sending and receiving uses “SFC 14”:
SFC14 (compressing sending)
SFC15 (compressing receiving)