WWW.SSTCOMM.COM
5
Output 001 byte
Output 002 bytes
Output 004 bytes
Output 008 bytes
Output 016 bytes
Output 032 bytes
Output 064 bytes
Output 128 bytes
Input / Output 001 byte
Input / Output 002 bytes
Input / Output 004 bytes
Input / Output 008bytes
Input / Output 016 bytes
Input / Output 032 bytes
Input / Output 064 bytes
Input / Output 128 bytes
[5] With 2 serial ports, serial I support RS-232,serial II support RS485,Two serial ports can be used as
communication ports, and they can communicate at the same time.
[6] The protocol type serial ports support: Modbus master, Modbus slave, self-defined protocol, User Config;
[7] Serial port parameters:
Operation mode: Half-duplex;
Baud rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 bps optional;
Data bits:7, 8;
Parity: None, Odd, Even, Mark and space optional;
Stop bits: 1,2 optional;
[8] Modbus master:
Function code: 01H, 02H, 03H, 04H, 05H, 06H, 0FH and 10H;
Format: RTU and ASCII;
Function: Cycle output, forbidden output and change of value output of write command;
Each master can configure up to 48 Modbus commands;
When serial port 1 (RS232 serial port) and serial port 2 (RS485 serial port) simultaneously connect the slave
equipment as the Modbus master, Serial port 1 supports connection of 1 Modbus slave device, and serial
port 2 can configure up to 3 nodes. When configuring serial port 2 as the Modbus master independently, it
Содержание GT200-PN-RS