The configuration interface is shown as below:
Baud Rate:
300,600, 1200, 2400,4800, 9600, 19200, 38400, 57600 and 115200bps optional
Data Bits:7,
8
Parity:
None, Odd, Even, Mark and Space optional
Stop Bits:
1, 2
Transmission Mode:
RTU, ASCII, valid when communication mode is poll mode
Response Timeout:
After the Modbus Master sends request, it waits the Modbus slave's response time;
range: 300~60000ms
Delay between Polls:
Delay between a response has been received and sending next request, the range
is 0~ 2500ms. Valid when communication is poll mode.
Output Mode
(valid when communication is poll mode)
Write command (command with data in request). There are three types of output command: Cycle,
Forbidden and Change of value.
Cycle: same as Modbus read command (command without data in request) output way
Forbidden: disable output of Modbus write command