WWW.SSTCOMM.COM
11
3 Quick Start Guide
3.1 Gateway Configuration
Configuring GT200-PN-RS needs the following steps:
a) Connect the power properly connect,GT200-PN-RS and PC through Ethernet cable and power on the
gateway;
b) Configure in the SST-TS-CFG according to users requirements;
c) Click "Download " button on the toolbar to download the configuration to the gateway;
d) When downloading is complete, it will give hints "whether to restart the gateway ", click "Yes ";
e) Configure some relevant modeling in STEP7, including module, IP address of target device and device
name;
f) Download the STEP7 modeling configuration to the PLC;
g) Waiting for about 10s, GT200-PN-RS will establish PROFINET connection with the PLC. At this time,
NS green on, MS green on.
Notes: How to find out how many GT200-PN-RS devices are in the LAN, including MAC address, IP address
and name of devices. Users can see chapter 3.4 Change Device IP and Name for help.
There are 3 necessary conditions which need to happen simultaneously when PROFINET device of SSTCOMM
is communicating with PLC:
a) The PROFINET device name must be the same as that of device in PLC modeling.
b) The PROFINET device IP address must be the same as that of device in PLC modeling.
c) The configuring module of PROFINET device (configuring through SST-TS-CFG) must be the same as that
in PLC modeling.
Note: The device name of GT200-PN-RS,which supports only a combination of lowercase letters and numbers, and
must begin with a lowercase letter.
The following are legal names: dut28 dut28nn32
The following are illegal names: 28dut
、
dut28$
、
dut28+uu
3.2 Software Instructions
Users need to install the gateway software SST-TS-CFG when configuring the gateway.
Users can use SST-TS-CFG to finish configuring GT200-PN-RS easily, including IP address, subnet mask,
gateway address, device name, baud rate of serial port, parity, stop bits, communication protocol selection and
Содержание GT200-PN-RS
Страница 53: ...WWW SSTCOMM COM 53...