background image

Oil Filter Service

To replace the filter cartridge, first drain the oil from the Geareducer 
case, then remove the drain plug from the oil filter case. See 

Figure  3

.

1.  Remove the four cap screws attaching the oil filter case cap, 

and remove cap.

2.  Remove and discard oil filter cartridge. Retain cartridge retainer 

washer and nut for re-installation.

3. Clean gasket material from filter case and cap.

4. Clean inside of filter case, cap and filter hardware.

5.  Install new filter cartridge. Reinstall cartridge retainer washer 

and nut. Install new cap gasket and reinstall filter case cap.

6.  Coat drain plug threads with Permatex Pipe Joint Com pound 

No. 51 or equal. Reinstall drain plug and tighten securely.

7.  After refilling unit with oil and operating unit, check all gasketed 

joints for oil seepage. Tighten flange bolts if necessary.

Check the oil level placard location each time the oil is changed. 
The “full” mark on the placard must be at the same elevation as 
the “full” arrow on the side of the Geare ducer case—see 

Figures 

and

 4

.

Sight glass vent must be kept open. Inspect at each oil 
change and clean when necessary. Inspect internal parts 
and inside of Geareducer case at each oil change—see sec-
tion on inspection of internal parts. Use oil recommended in  
Table 1 for the proper atmospheric temperature range.

VENT

OIL LEVEL

GAUGE

OIL LEVEL

PLACARD

FULL

ADD

OIL

NOTICE

CHECK OIL LEVEL TEN

MINUTES AFTER

FAN STOPS ROTATING

FILL AT GEAREDUCER

REFER TO SERVICE MANUAL

FOR OIL CHANGE AND

MAINTENANCE RECOMMENDATIONS

SPX COOLING TECHNOLOGIES

OVERLAND PARK, KS  USA

92-110A

Figure 3 

Cross section of oil filter

Figure 4 

Sight glass gauge assembly

operation and service

Содержание Marley Geareducer 32.2 Series

Страница 1: ...Geareducer model 32 2 INSTALLATION OPERATION MAINTENANCE Z0238997_B ISSUED 09 2016 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual...

Страница 2: ...ed via the filler neck or pumped in through the drain connection this lubricant will not reduce the overall level of protection however if the unit is operated for any amount of time the Pre Commissio...

Страница 3: ...should occur refer to Marley Field Repair Manual for Series 32 2 Geareducer Repair and Overhaul Geareducers can be repaired in the field however ma jor repairs require the use of a fully equipped mac...

Страница 4: ...4 Detail A Spiral Bevel Gear Tooth Pattern Detail B Helical Gear Tooth Pattern operation and service...

Страница 5: ...used oil in an appropriate container 2 With Geareducer drained the three way valve turned clockwise and the pipe plug removed connect fill source either a street ell and stand pipe of sufficient lengt...

Страница 6: ...perating unit check all gasketed joints for oil seepage Tighten flange bolts if necessary Check the oil level placard location each time the oil is changed The full mark on the placard must be at the...

Страница 7: ...re Air Temperature at Geareducer Below 110 F 43 C Above 110 F 43 C ISO 150 ISO 220 operation and service Maintenance Service Monthly Semi annually Seasonal Startup or Annually Geareducer Drive Inspect...

Страница 8: ...n the interest of technological progress all products are subject to design and or material change without notice Geareducer 32 2 US E R MAN UAL SPX COOLING TECHNOLOGIES INC 7401 WEST 129 STREET OVERL...

Отзывы: