background image

operation and service

Corrosion and Dry Start-Up Protection

Marley Geareducers utilize iron and steel materials, which if not 
maintained correctly, may degrade. While some external corrosion 
is acceptable, an internal lubrication film must be maintained at all 
times to protect the working components against corrosion and 
potential startup damage. The following information describes 
methods of operation and preventive measures to ensure suitability 
for long-term operation.

Status Definitions

Pre-Commission

  

  Duration* = Up to 4 months after receipt.
  * export shipment status duration is reduced by 1 month
   This is the as-shipped condition, which contains a factory rust-

proofing coating on the interior of the unit as well as a grease 
coating on the exposed shaft surfaces. 

   If the cooling tower is not ready for operation at the time of 

status expiration, steps must be taken to place the Geareducer 
into 

Long-Term Storage or Downtime 

status.

Operational

 

 

 This stage is initiated upon the first motor driven sequence. The 
Geareducer is now considered as being placed into regular 
service and operation.

Idle

  Duration = 2 to 4 weeks.
   This stage is a suspension in operational status and lasts up 

to two 2 weeks. The duration may be doubled by completing 

Run Cycle.

   It is not recommended to extend the idle status more than once 

in any given sequence.

  A common application is during a temporary outage

Seasonal Shutdown

  Duration = Up to 4 months after operational is suspended.
  This stage may be considered an extended idle condition.
  Requires additional preventive maintenance. 

Long-Term Storage or Downtime

  Duration = Indefinite.
  Requires long-term preventive measures. 

Run Cycle

   Defined as full speed operation for a minimum of 30 minutes. 

This recoats all internal components and surfaces with lubri-
cant and also helps to expel some moisture that may have 
accumulated from daily ambient condition cycling.

As shipped, a Marley Geareducer is protected internally against 
corrosion with machine enamel on un-machined parts and with 
rust-proofing oil and grease on machined surfaces. These coatings 
normally protect the Geareducer against corrosion for the duration 
of the 

Pre-Commission

 phase. Adding normal lubricant to the 

unit will dissolve the rust-proofing oil in the Geareducer sump. 
Provided it is added via the filler-neck or pumped in through the 
drain connection, this lubricant will not reduce the overall level 
of protection however, if the unit is operated for any amount of 
time, the 

Pre-Commission

 period is depleted and the unit is now 

considered to be in 

Operational

 status. 

Check the Geareducer exterior yearly. Touch up with paint as 
required. Exposed pipe threads are coated to prevent corrosion. 
Touch up coating as required.

Initial Operation

Priming

Due to lack of control over facility operational readiness, site  
ambient conditions or storage practices, etc., it is recommended  
to supplement lubricant prior to initial operation. The same fill 
lubricant should be poured or pumped into the port above the 
interstage shaft. Remove pipe plug in center of Interstage Bear-
ing Cap to expose port. Refer to 

Figure 1

. If additional oil is be-

ing used, an amount of 1 to 1 1/2 quarts should be used. If the 
lubricant is being pumped from the sump bulk volume, at least 
1 quart 

should 

be transferred. In either case, this priming step 

should be performed within 5 days of initial operation. If a delay 
occurs and the 5 day duration is exceeded, repeat the process. 
In either case, this priming step should be performed 

while rotat-

ing the gear train by hand

 and within 5 days of initial operation.

Warning 

– Operating the Geareducer at an oil level other than 

between the Add and Full levels may damage the unit and possibly 
mating equipment. This could also escalate to a safety concern 
for nearby personnel. 
The Geareducer must be filled with oil to the Full oil level mark on 
the Geareducer case before it is placed in operation. If the unit 
is being taken out of 

Long-Term Storage or Downtime

, the oil 

should be drained down to the Full operating level. If drain-down 
occurs within 5 days of the initial startup, the above priming se-
quence may be skipped. See 

Service and Lubrication

 section 

for oil filling instructions.
Geareducers supplied with new cooling towers include oil for the 
initial filling and in some cases, will also ship with an additional 
amount required to place the unit into 

Long-Term Storage or 

Downtime

 status. Normally, oil is not furnished with Geareducers 

supplied as a spare or on replacement orders. Before operating 
the mechanical equipment, check to be sure the oil level is at the 
Full mark at the Geareducer and that the external gauge placard 
Full mark corresponds with the Full level in the Geareducer. Check 
oil lines to be sure there are no leaks.

Содержание Marley Geareducer 32.2 Series

Страница 1: ...Geareducer model 32 2 INSTALLATION OPERATION MAINTENANCE Z0238997_B ISSUED 09 2016 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual...

Страница 2: ...ed via the filler neck or pumped in through the drain connection this lubricant will not reduce the overall level of protection however if the unit is operated for any amount of time the Pre Commissio...

Страница 3: ...should occur refer to Marley Field Repair Manual for Series 32 2 Geareducer Repair and Overhaul Geareducers can be repaired in the field however ma jor repairs require the use of a fully equipped mac...

Страница 4: ...4 Detail A Spiral Bevel Gear Tooth Pattern Detail B Helical Gear Tooth Pattern operation and service...

Страница 5: ...used oil in an appropriate container 2 With Geareducer drained the three way valve turned clockwise and the pipe plug removed connect fill source either a street ell and stand pipe of sufficient lengt...

Страница 6: ...perating unit check all gasketed joints for oil seepage Tighten flange bolts if necessary Check the oil level placard location each time the oil is changed The full mark on the placard must be at the...

Страница 7: ...re Air Temperature at Geareducer Below 110 F 43 C Above 110 F 43 C ISO 150 ISO 220 operation and service Maintenance Service Monthly Semi annually Seasonal Startup or Annually Geareducer Drive Inspect...

Страница 8: ...n the interest of technological progress all products are subject to design and or material change without notice Geareducer 32 2 US E R MAN UAL SPX COOLING TECHNOLOGIES INC 7401 WEST 129 STREET OVERL...

Отзывы: