background image

15

troubleshooting

SAFETY FIRST–The CP cooling tower has been designed to provide a safe working environment while either 
operating or shut down. The ultimate responsibility for safety rests with the operator and owner. When water 
flow to the tower is shut off or when portions of the tower require maintenance, temporary safety barricades may 
be required around openings and fall protection equipment should be utilized where appropriate for compliance 
with OSHA and CE regulations, standards and good safety practices.

Trouble

Cause

Remedy

Unusual fan drive 
vibration

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment and 
supports.

Fan

Make certain all blades are as far from center of fan as safety devices 
permit. All blades must be pitched the same. See “Fan IOM Manual.” Clean 
off deposit build-up on blades

Fan noise

Blade rubbing inside of fan hood

Adjust to provide blade tip clearance

Loose bolts in blade clamps

Check and tighten if necessary.

Scale or foreign 
substance in circulating 
water system

Insufficient blowdown

See "Water Treatment" section of this manual.

Water treatment deficiency

Consult competent water treating specialist. See "Water Treatment" 
section of this manual

Condensing temperature 
too warm. 
See “Cooling Tower 
Operation.”

Entering wet bulb temperature is above design

Check to see if local heat sources are affecting evaporative condenser. 
See if surrounding structures are causing recirculation of evaporative 
condenser discharge air. Discuss remedy with Marley representative.

Design wet bulb temperature was too low.

May have to increase evaporative condenser size. Discuss remedy with 
Marley representative

Actual process load greater than design

May have to increase evaporative condenser size. Discuss remedy with 
Marley representative

Overpumping

Reduce water flow rate over evaporative condenser to design conditions.

Evaporative condenser starved for air

Check motor current and voltage to be sure of correct contract 
horsepower. Repitch fan blades if necessary. Clean eliminators. Check to 
see if nearby structures or enclosing walls are obstructing normal airflow 
to evaporative condenser. Discuss remedy with Marley representative.

Excessive drift exiting 
evaporative condenser

Spray system malfunction

Inspect spray system for proper operation. Correct as necessary.

Faulty drift elimination

Check to see that the eliminators are clean, free of debris and installed 
correctly. Clean if necessary. Replace damaged or worn out components.

Содержание MARLEY CP

Страница 1: ...CP cooling tower OPERATION MAINTENANCE uk_Z1045767_A ISSUED 8 2018 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual...

Страница 2: ...to important information concerning the life of the product Indicates presence of a hazard which can cause severe personal injury death or substantial property damage if ignored Indicates presence of...

Страница 3: ...the cold water collection basin sump and screens Use a water hose to flush cold water collection basins Fill the cold water collection basin and circulating water system until the op erating water lev...

Страница 4: ...l to come up to operating temperature and check the motor load with a watt meter ortakeoperatingvoltandamperereadingsandcalculatemotorhp Pitch fans if required to pull correct contract horsepower when...

Страница 5: ...this includes theairinletandadjacentstructuralframing Yourunderstandingofcoldweather operation will be enhanced if you read Cooling Towers and Freezing Weather Technical Report H 003 available at spx...

Страница 6: ...ing results and the least maintenance cost SPX recommends setting up a regular inspection schedule to insure effective safe operation of the cooling tower Use the schedule on page 19 to obtain continu...

Страница 7: ...R Make weekly and monthly oil checks Inspect internal part during seasonal oil change Lubricate and maintain each gear motor in ac cordance with the manufacturer s instructions If repair work is neces...

Страница 8: ...4 concentrations circulating water will contain four times as much dissolved solid as the make up water providing none of the solids form scale or are otherwise removed from the system CHEMICAL TREATM...

Страница 9: ...ids or by contamination of the circulating water with foam causing compounds This type of foaming can sometimes be minimized by increasing the blowdown but in some cases foam depressant chemicals must...

Страница 10: ...ate walking surface on fill to avoid crushing Recommended walking surface would be a minimum of 15mm thick plywood measuring at least 30cm x 60cm Spare Parts SPX Cooling Technologies manufactures and...

Страница 11: ...he gear motor space heater option Gear motor Downtime for 3 months or more 1 Follow the manufacturer s instruction for shutdown instructions 2 If the motors do not have space heaters operate mechanica...

Страница 12: ...rtup section of this manual Cooling towers must be cleaned and disinfected regularly in accordance with local public health services and recommendations Workersperform ing decontamination procedures m...

Страница 13: ...Fan Hood Ladders Platform and Doors Inspect for clogging M M W W Check for unusual noise or vibration D D Inspect keys keyways and set screws S S Make sure vents are open S Lubricate grease R Check o...

Страница 14: ...nbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan User Manual Check for drag in fan drivetrain and from damaged bearings Wr...

Страница 15: ...ent water treating specialist See Water Treatment section of this manual Condensing temperature too warm See Cooling Tower Operation Entering wet bulb temperature is above design Check to see if local...

Страница 16: ...ition 1 Good 2 Keep an eye on it 3 Needs immediate attention 1 2 3 Comments Structure Casing Material Structural Material Fan Deck Material Stairway Material Ladder Material Handrails Material Interio...

Страница 17: ...facturer Fixed Pitch Adjustable Pitch Diameter Number of Blades Blade Material Hub Material Hub Cover Material Blade Assembly Hardware Tip Clearance min max Vibration Level Fan Cylinder Height Mech Eq...

Страница 18: ...ESERVED In the interest of technological progress all products are subject to design and or material change without notice SPX COOLING TECHNOLOGIES UK LTD 3 KNIGHTSBRIDGE PARK WORCESTER WR4 9FA UK 44...

Отзывы: