troubleshooting

Trouble

Cause

Remedy

Motor will not start

Power not available at motor terminals

Check power at starter. Correct any bad connections between the control 
apparatus and the motor.

Check starter contacts and control circuit. Reset overloads, close contacts, 
reset tripped switches or replace failed control switches.

If power is not on all leads at starter, make sure overload and short circuit 
devices are in proper condition

Wrong connections

Check motor and control connections against wiring diagrams.

Low voltage

Check nameplate voltage against power supply. Check voltage at motor 
terminals.

Open circuit in motor winding

Check stator windings for open circuits.

Motor or fan drive stuck

Disconnect motor from load and check motor and fan drive for cause of 
problem.

Rotor defective

Look for broken bars or rings.

Unusual motor noise

Motor running single-phase

Check motor and attempt to start it. Motor will not start if single-phased. 
Check wiring, controls and motor.

Motor leads connected incorrectly

Check motor connections against wiring diagram on motor.

Bad bearings

Check lubrication. Replace bad bearings.

Electrical unbalance

Check voltages and currents of all three lines. Correct if required.

Air gap not uniform

Check and correct bracket fits or bearing.

Rotor unbalance

Rebalance

Cooling fan hitting end belt guard

Reinstall or replace fan.

Motor runs hot

Wrong voltage or unbalanced voltage

Check voltage and current of all three lines against nameplate values.

Overload

Check fan blade pitch. See “Fan User Manual.” Check for drag in fan 
drivetrain and from damaged bearings.

Wrong motor RPM

Check nameplate against power supply. Check RPM of motor and drive 
ratio.

Bearing overgreased

Remove bearing reliefs. Run motor up to speed to purge excessive 
grease.

Wrong lubricant in bearings

Change to proper lubricant. See motor manufacturer's instructions.

One phase open

Stop motor and attempt to start it. Motor will not stat if single-phased. 
Check wiring, controls and motor.

Poor ventilation

Clean motor and check ventilation openings. Allow ample ventilation 
around motor.

Winding fault

Check with ohmmeter.

Bent motor shaft

Straighten or replace shaft.

Insufficient grease

Remove plugs and regrease bearings.

Too frequent starting or speed changes

Limit cumulative accelerations time to a total of 30 seconds/hour. Set on/
off or speed change set points farther apart. Consider installing a Marley 
VFD drive for fine temperature control.

Deterioration of grease or foreign material in grease

Flush bearings and relubricate.

Bearings damaged

Replace bearings.

Motor does not come up 
to speed

Voltage too low at motor terminals because of line 
drop

Check transformer and setting of taps. Use higher voltage on transformer 
terminals or reduce loads. Increase wire size or reduce inertia.

Broken rotor bars

Look for cracks near the rings. A new rotor may be required. Have motor 
service person check motor.

Wrong motor rotation

Wrong sequence of phases

Switch any two of the three motor leads.

Содержание MARLEY CP

Страница 1: ...CP cooling tower OPERATION MAINTENANCE uk_Z1045767_A ISSUED 8 2018 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual...

Страница 2: ...to important information concerning the life of the product Indicates presence of a hazard which can cause severe personal injury death or substantial property damage if ignored Indicates presence of...

Страница 3: ...the cold water collection basin sump and screens Use a water hose to flush cold water collection basins Fill the cold water collection basin and circulating water system until the op erating water lev...

Страница 4: ...l to come up to operating temperature and check the motor load with a watt meter ortakeoperatingvoltandamperereadingsandcalculatemotorhp Pitch fans if required to pull correct contract horsepower when...

Страница 5: ...this includes theairinletandadjacentstructuralframing Yourunderstandingofcoldweather operation will be enhanced if you read Cooling Towers and Freezing Weather Technical Report H 003 available at spx...

Страница 6: ...ing results and the least maintenance cost SPX recommends setting up a regular inspection schedule to insure effective safe operation of the cooling tower Use the schedule on page 19 to obtain continu...

Страница 7: ...R Make weekly and monthly oil checks Inspect internal part during seasonal oil change Lubricate and maintain each gear motor in ac cordance with the manufacturer s instructions If repair work is neces...

Страница 8: ...4 concentrations circulating water will contain four times as much dissolved solid as the make up water providing none of the solids form scale or are otherwise removed from the system CHEMICAL TREATM...

Страница 9: ...ids or by contamination of the circulating water with foam causing compounds This type of foaming can sometimes be minimized by increasing the blowdown but in some cases foam depressant chemicals must...

Страница 10: ...ate walking surface on fill to avoid crushing Recommended walking surface would be a minimum of 15mm thick plywood measuring at least 30cm x 60cm Spare Parts SPX Cooling Technologies manufactures and...

Страница 11: ...he gear motor space heater option Gear motor Downtime for 3 months or more 1 Follow the manufacturer s instruction for shutdown instructions 2 If the motors do not have space heaters operate mechanica...

Страница 12: ...rtup section of this manual Cooling towers must be cleaned and disinfected regularly in accordance with local public health services and recommendations Workersperform ing decontamination procedures m...

Страница 13: ...Fan Hood Ladders Platform and Doors Inspect for clogging M M W W Check for unusual noise or vibration D D Inspect keys keyways and set screws S S Make sure vents are open S Lubricate grease R Check o...

Страница 14: ...nbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan User Manual Check for drag in fan drivetrain and from damaged bearings Wr...

Страница 15: ...ent water treating specialist See Water Treatment section of this manual Condensing temperature too warm See Cooling Tower Operation Entering wet bulb temperature is above design Check to see if local...

Страница 16: ...ition 1 Good 2 Keep an eye on it 3 Needs immediate attention 1 2 3 Comments Structure Casing Material Structural Material Fan Deck Material Stairway Material Ladder Material Handrails Material Interio...

Страница 17: ...facturer Fixed Pitch Adjustable Pitch Diameter Number of Blades Blade Material Hub Material Hub Cover Material Blade Assembly Hardware Tip Clearance min max Vibration Level Fan Cylinder Height Mech Eq...

Страница 18: ...ESERVED In the interest of technological progress all products are subject to design and or material change without notice SPX COOLING TECHNOLOGIES UK LTD 3 KNIGHTSBRIDGE PARK WORCESTER WR4 9FA UK 44...

Отзывы: